Eclipse EC-P50 Installation Manual - page 32
32
P0016-LI-03.01
No
Type & Description
0025 PSTN
Fault
This output type activates when a fault is detected on the
PSTN connected to the control panel.
0026
PSTN Off Hook
This output type activates when an off-hook condition is
detected on the PSTN connected to the control panel.
0027 PSTN
Ringing
This output type activates when ringing is detected on the
PSTN connected to the control panel.
0028 Battery
Fault
This output type activates when a fault is detected with the
control panel standby battery.
0029
Box Tamper Fault
This output type activates when the control panel box
tamper is open.
0030
Bell Tamper Fault
This output type activates when the control panel bell
tamper is open.
0031 Engineer
on
Site
This output type activates when the engineer is logged on.
0032 Detector
Reset
This output type is normally active and is used for powering
devices that require their power supply to be removed in
order to reset them. The output deactivates for 5 seconds at
the start of exit mode and when the system is reset.
0033 Detector
Latch
This output type is used to latch the alarm condition on
detection devices that have a latch input.
0034 System
Low
Volts
This output type activates when a low voltage fault is
detected with the control panel standby battery.
0035 In
Exit
This output type activates when the system is in exit mode.
0036 In
Entry
This output type activates when the system is in entry mode.
0037
In Second Entry
This output type activates when the system is in second
entry mode.
0038 In
Alarm
This output type activates when any alarm is generated.
0039 Auxiliary
Alarm
This output type activates when an auxiliary alarm is
generated.
0040 Warning
Alarm
This output type activates when a warning alarm is
generated.
0041 Keypads
Locked
This output type activates when a security key is active.
0042 Output
Fault
This output type activates when a fault is detected on one of
the monitored control panel outputs.
0043 Call
Engineer
This output type activates when the system requires an
engineer access code in order to reset the system.
0044 Device
Fault
This output type activates when a device fault is detected.
0045 Service
Required
This output type activates when the service timer expires.
0046 Cleaner
Bypassed
This output type activates when a “Cleaner Bypass” is
invoked.
0047 2-Wire
Smoke
This output type is specifically designed for use with “Panel
Output 5”, when connecting 2-Wire Smoke Sensors.
0048
2-Wire Smoke Alarm
This output type activates when a 2-Wire smoke alarm is
generated.
No
Type & Description
0049
2-Wire Smoke Fault
This output type activates when a 2-Wire smoke fault is
generated.
0050 Door
Access
This output type activates for 30 seconds when any valid
user code is entered.
0051 Alarm
Test
This output type activates when the user select the alarm
sounder test.
0052
Panel AC On
This output type activates when the mains supply is present.
0053 Reset
Active
This output type activates for 10 seconds after a user resets
the system.
0054 Arming
Failed
This output type activates when the system fails to arm.
0055 Confirm
Device
This output type activates when the number of devices on
the network differ to the number confirmed by the engineer.
0056
Stay Arm 1
This output type activates when the system is armed in the
Stay 1 mode.
0057
Stay Arm 2
This output type activates when the system is armed in the
Stay 2 mode.
0058
Stay Arm 3
This output type activates when the system is armed in the
Stay 3 mode.
Group 02: Control Timer
The EC-P50 has 5 control timers each timer can be assigned to
an output:
No
Type & Description
0201
Control Timer 1
This output type activates when Control Timer 1 is on and
deactivates when Control Timer 1 is off.
0202-
0205
Control Timer 2 - 5
As Control Timer 1.
Group 03: Remote Control
There are 5 remote controlled outputs, which can be assigned to
an output:
No
Type & Description
0301 Remote
Control
1
This output type is switched on and off via the
UDL
software,
smart phone app and via a touch tone telephone.
0302-
0305
Remote Control 2 - 5
As Remote Control 1.
Group 04: Link Control
There are 99 Link controlled outputs, which can be assigned to an
output:
No
Type & Description
0401
Link Control 01
This output type is controlled by a combination of linked
inputs.
0402-
0499
Link Control 02 - 99
As Link Control 01.