4.8 Display
Home-Bypass
Zones
With the system in “OFF” mode,
Check which zones have been set as Home-Bypass Zones as follows:
Two short beeps and the zone indicators for the Home-Bypass Zones will illuminate for a few
seconds.
4.9 Set delay time
★ When the system is put in “OUT” mode, there is a 30 seconds (factory preset, can be changed
by user to 15 or 45 seconds) delay time before the alarm will be activated. The delay time is
to give the user enough time to exit or enter the premises before the alarm is activated. User
may select the delay timer as follows:
With the system in “OFF” mode,
Set entrance / exit delay timer:
N =1 for 15 sec
N =2 for 30 sec
N =3 for 45 sec
Two short beeps indicate the command is successful and a long beep indicates the command is
rejected.
4.10 Set siren & strobe duration
★ The siren & strobe
is preset at the factory to a duration of 3 minutes. The alarm will stop by
itself after this preset
duration and the alarm hold indication (illuminated zone indicator) will
be on. To change the duration, do as follows:
With the system in “OFF” mode,
Set siren & strobe duration timer:
N =0 for continuously (set the siren duration by jumper selection, refer Section 3.4, page 12.)
N =1 for 1 min
N =2 for 3 min
N =3 for 10 min
Two short beeps indicate the command is successful and a long beep indicates the command is
rejected.
4.11 Walk Test command
With the system in “OFF” mode,
Enable walk test mode as follows:
Two short beeps confirm command is accepted and Walk Test mode is activated.
Trigger all the zones and the corresponding zone indicators will illuminate.
Exit walk test mode as follows:
Two short beeps and zone indicators will turn off, Walk Test mode is exited.
*
*
*
*
*
*
*
*
*
*
*
*
#
*