Pacific Energy NEO 2.5 Installation And Operating Instructions Manual - page 11
110714-24
NEO25 11
Warning: Under no circumstances is this heater to be installed
in a makeshift or "temporary" manner. It may be fi red only
after the following conditions have been met.
* DO NOT ATTEMPT TO CONNECT THIS HEATER TO
ANY AIR DISTRIBUTION DUCT.
* Outside combustion air or fresh air into the room may be
required in your area, consult local building codes (see
Combustion Air section).
- The services of a competent or certifi ed installer, (certifi ed
by the Wood Energy Technical Training program (WETT) - in
Canada,or the Hearth Education Foundation (HEARTH) - in
U.S.A.,) are strongly recommended.
BOTH CHIMNEY SYSTEM AND CONNECTOR MUST BE
6"(150mm) DIAMETER AND LISTED TO: IN CANADA -
IN CANADA -
ULC S-641 LISTED CONNECTOR AND ULC-S-629 LISTED
ULC S-641 LISTED CONNECTOR AND ULC-S-629 LISTED
CHIMNEY,
CHIMNEY,
IN USA - UL-103 HT LISTED CONNECTOR
IN USA - UL-103 HT LISTED CONNECTOR
AND CHIMNEY
AND CHIMNEY
Clearances
1. This heater may be installed using a single-wall connector
(smoke pipe) or listed double-wall connector (see Mobile
Home installation).
2. Clearances to combustible surfaces and materials using
single-wall connector are shown in Figure #6, page 12.
Clearances may be reduced with various heat insulating
materials. Consult local fi re codes and authorities for
approval.
3. Alternately, for close clearances, use a listed double-wall
connector. See Fig #6 & #7, page 12.
It is possible to store wood between the stove supports,
underneath the unit. The wood must not extend further
forward than fl ush with the supports. Do not store paper or
other stove lighting devices within the pedestal area. Although
this is possible it is not recommended. NOTE: Refer to local
fi re codes, CAN-B365 in Canada and NFPA 211 in the U.S..
Chimney and Connector
Connect to a listed chimney or a chimney suitable for use
with solid fuel that is lined and in good condition and meets
local building codes. The chimney fl ue size should be the
same as the stove outlet for optimal performance. Reducing
or increasing the fl ue size may adversely affect stove
performance. Chimney fl ue exit is to be 3 feet (1 m.) above
roof and two feet (0.6 m.) above highest projection within 10
feet (3 m.). The installation must meet all local codes. Do not
connect this unit to a chimney fl ue serving another appliance.
Minimum system height is 15 feet (4.6 m.) (measured from
base of appliance).
Double-Wall Connector
-
Use a listed double-wall connector.
- Install all components to the chimney connector
manufacturer's installation requirements.
Single-Wall Connector
Smoke pipe must be:
* as short and straight as possible, use six inch
diameter, 24 gauge black pipe that is clean and in new
condition.
* secured at every joint and collar with 3 sheet metal screws.
* installed with the crimped or male ends pointing down.
This will carry any liquid creosote or condensation back
into the stove.
* The chimney connector shall not pass through an attic,
roof space, closet or similar concealed space, fl oor, or
ceiling. Where passage through a wall, or partition of
combustible material is desired, the installation shall
conform to CAN/CSA-B365, Installation Code for Solid-
Fuel-Burning Appliances and Equipment or in the U.S.,
NFPA 211: Standard for Chimneys, Fireplaces, Vents, and
Solid Fuel-Burning Appliances.
Procedure
1. If a listed chimney and double-wall connector is to
be connected to the stove, install all components to
the chimney manufacturer's installation requirements.
(Outside combustion air may be required, consult local
building codes. See Combustion Air section on page 10.)
2. If it is desirable to use smoke pipe in conjunction with the
insulated chimney, see step 4.
3. If a roof or ceiling support is used in the installation, you
will fi nd the chimney manufacturer's complete instructions
packed with the roof support.
4. To start installing smoke pipe (chimney connector), slip
crimped edge of the pipe inside the stove collar. Use
holes provided in collar to secure pipe with three screws.
5. Install the remaining lengths of pipe one on top of the
other to the fi nished height of the chimney connector and
secure to each other.
Residential Installation