Protherm 100 Manual for instruction and use - page 11
20
21
The PROTHERM KLO/KLO EKO gas-fired
boilers are covered by a warranty speci-
fied in the Warranty Certificate, Service
Book and the conditions defined in these
Operating Instructions.
Warranty and Warranty Terms and Conditions
Completeness of the Delivery
Delivery of the actual boiler
The PROTHERM KLO/KLO EKO boilers
are delivered completely assembled and
with their functions tested.
Part of the delivery is the following docu-
mentation:
– Operating Instructions,
– Product Quality and Completeness
Certificate,
– Warranty Certificate,
– Service Book,
– Directory of Service Centres.
Customised delivery
The following optional accessories can be
supplied with the boiler:
– room control unit,
– RVA 43.222 equithermal control unit,
– gas leak detection system,
– UHW heating reservoir,
– three-way distribution valve.
Transportation and Storage
The manufacturer suppliers the boiler
standing on a palette, to which it is se-
cured against moving (by screws). When
manipulating and storing the boiler, do not
apply force on the boiler’s covers! Boilers
without a palette are manipulated on the
boiler’s body base (see Chapter X).
Boilers must be stored in a room, which
meets at least the basic environmental
conditions (non-corrosive, maximum hu-
midity 75%, temperature between 5°C
and 55°C, low dust, no biological agents).
Technical specifications of KLO Series boilers
Boiler type . . . . . . . . . . . . . . . . . .
65 KLO
. . . . . . .
85 KLO
. . . .
100 KLO
. . . . .
130 KLO
. . . . .
150 KLO
Number of elements . . . . . . . . . . . . . 8 . . . . . . . . . . . 10 . . . . . . . . . . 12 . . . . . . . . . . 15 . . . . . . . . . . .17
Version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B11BS
Appliance category . . . . . . . . . . . . II2H3P
I2H . . . . . . . . . I2H . . . . . . . . I2H . . . . . . . . . . I2H
Ignition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . by electric spark
Fuel/ inlet gauge pressure . . . . . . . . . . . . . . . . . . natural gas / 2 kPa, propane / 3.7 kPa
Output stage I / II - ZP (kW) . . . . . 49 / 65 . . . . . . . 59 / 85
70 / 99
91 / 130
105 / 150
Output stage I / II - P(kW) . . . . . . . - / 55 . . . . . . . . . . - . . . . . . . . . . - . . . . . . . . . . - . . . . . . . . . . . . -
Input stage I / II - ZP (kW) . . . . 53,5 / 70,6 . . . . 64,7 / 92,4 . . . 76,8 / 107,6 . . 98,4 / 141,3 . . . 115,3 / 163
Input stage I / II – P (kW) . . . . . . .- / 60,1 . . . . . . . . . - . . . . . . . . . . - . . . . . . . . . . - . . . . . . . . . . . . -
Efficiency ZP / P (%) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91 / 91
Consumption
Natural gas (cu.m / h) . . . . . . . . . 5,7 / 9,5 . . . . . . 6,8 / 9,8 . . . . . 8,1 / 11,3 . . . 10,4 / 14,9 . . . . 12,2 / 17,2
Propane (kg/h) . . . . . . . . . . . . . . . . 6,1 . . . . . . . . . . . - . . . . . . . . . . . - . . . . . . . . . . - . . . . . . . . . . . . -
Burner jet diameter (mm)
Natural gas / Propane . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2,7 / 1,55
Number of burner tubes (pieces) . . . 7 . . . . . . . . . . . . 9 . . . . . . . . . 11 . . . . . . . . . 14 . . . . . . . . . . . 16
Volume of water in the heating body (l)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 27,7 . . . . . . . . . 34,3 . . . . . . . . 40,9 . . . . . . . . 50,8 . . . . . . . . . 57,4
Max. operating temperature (°C) . . . . . . . . . . . . . . . . . . 85 (80°C for open systems)
Max. operating gauge pressure VV (bar) . . . . . . . . . . . . . . . . . . . . . . 4
Min. operating gauge pressure (bar) . . . . . . . . . . . . . . . . . . . . . . . . . 0,3
Test water gauge pressure (bar) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1/N/PE AC 230 V, 50 Hz/TN-S
Electric input (W) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Electric protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP 41
Noise level (dB) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . do 55
Removal of combustion gases
Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .through chimney
Flue diameter (mm) . . . . . . . . . . . . 180 . . . . . . . . . . 200 . . . . . . . . . 220 . . . . . . . . . 220 . . . . . . . . . . 250
Minimum chimney thrust (mbar) . . . . . . . . . . . . . . . . . . . . . . . .0,025 / 2,5 Pa
TTemperature of combustion fumes at max. output ZP / P(°C) . 129 / 115
NO
X
class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Class III
Combustion fumes flow in weight terms at min./max. output
Natural gas (g/s) . . . . . . . . . . . . . 44 / 46,3 . . . . . . 53 / 60,5 . . . . . 63 / 70,5 . . . . . 81 / 92,6 . . . . . . 95 / 107
Propane (g/s) . . . . . . . . . . . . . . . .- / 45,7 . . . . . . . . . - . . . . . . . . . . . - . . . . . . . . . . . .- . . . . . . . . . . . . -
Connection dimensions
Gas / heating water connection . . . . . G1" / G6/4"
Boiler width (mm) . . . . . . . . . . . . . . 850 . . . . . . . . . 1010 . . . . . . . 1170 . . . . . . . . 1410 . . . . . . . . . 1570
Boiler height / depth (mm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1195 / 960
Boiler weight (kg) . . . . . . . . . . . . . . 258 . . . . . . . . . . 332 . . . . . . . . 395 . . . . . . . . . 482 . . . . . . . . . 546