Protherm 100 Manual for instruction and use - page 17
32
33
uring point is situated on the burner plate
console.
5. Start up the boiler.
6. Let the operating pressure on the burn-
er stabilise for a while before starting the
adjustment.
7. Take orientation reading of the gas
pressure (the values must correspond to
the values specified in Table X).
8. Remove the aluminium plug on gas
valve 1 and lightly turn the plastic output
adjusting screw found inside.
9. Fold the protective plastic HIGH/LOW
modulator cover on gas valve 2.
10. Using the HIGH/LOW switch, set the
boiler to nominal output (two flames).
11. Insert an 8 mm spanner on the gas
valve modulator 2 nut and by turning it
clockwise or anticlockwise adjust the boil-
er’s nominal output. Adjust the low output
by turning the modulator screw clockwise
or anticlockwise using a 3.5 mm wide flat
screwdriver.
12. Check the output setting.
13. Make sure that all measuring points
are properly secured and no gas leaks
from them.
k
Table 4:
Pressure of gas settings for KLO – natural gas / propane.
Model
65 KLO
85 KLO
100 KLO
130 KLO
150 KLO
Low power (mbar)
7,3 / -
6,7
6,2
7,2
6,6
Maximum power (mbar)
12,4 / 31,4
12,8
11,3
12,3
12,9
Ø
jet of main burner (mm)
2,7 / 1,55
2,7
Ø
jet of operat. burner (mm)
0,45 / 0,24
0,45
0,45
0,45
0,45
Table 5:
Pressure of gas settings for KLO EKO – natural gas / propane
Model
65 KLO EKO
85 KLO EKO
100 KLO EKO
130 KLO EKO 150 KLO EKO
Low power (mbar)
7,8 / -
7,4
6,6
7,7
7,1
Maximum power (mbar)
13,8 / 28,4
14,2
13,3
13,7
13,7
Ø
jet of main burner (mm)
2,6 / 1,6
2,6
Ø
jet of operat. burner (mm)
0,45 / 0,24
0,45
0,45
0,45
0,45