Assembling the boiler after delivery
The boilers Series KLO / KLO EKO are
for transportation reasons delivered with
the thrust breaker installed in a horizontal
position. After the boiler has been deliv-
ered to the point of installation, the thrust
breaker must be installed in the operating
position. The installation procedure is as
follows:
1. Remove the top boiler cover which is
fastened with two self-cutting screws.
2. After having removed the top cover, dis-
mantle the thrust breaker. The thrust
breaker is attached with three self-cut-
ting screws to the internal boiler bulkhe-
ad (Fig. 6).
3. Pull out part of the thrust breaker and
rotate it so that the combustion fumes
neck is pointing vertically upwards. In-
sert this part into the counter-part and
secure it with ten self-cutting screws.
The line in Fig. 7 indicates the joining of
the two thrust breaker parts.
4. After assembling the thrust breaker, you
must install a sensor (capillary) of the
combustion fumes thermostat, which is
located inside the boiler, next to the
thrust breaker. Insert the sensor in the
hole at the back of the thrust breaker
and fasten it with the clip and the self-
-cutting screw provided for this purpose
(Fig. 8).
Boiler covers
The front cover is removable. It is held
by spring clips which are attached in the
top corners. When removing the cover,
the pressure of the spring clips gripping
the holding pins must be overcome. After
dropping it down first, the cover can be
completely removed.
Technical specifications of KLO EKO Series boilers
Boiler type . . . . . . . . . . . . . . . .
65 KLO EKO
. . .
85 KLO EKO
100 KLO EKO
130 KLO EKO
150 KLO EKO
Number of elements . . . . . . . . . . . . . 8 . . . . . . . . . . . 10 . . . . . . . . . . 12 . . . . . . . . . . 15 . . . . . . . . . . .17
Version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B11BS
Appliance category . . . . . . . . . . . . II2H3P
I2H . . . . . . . . . I2H . . . . . . . . I2H . . . . . . . . . . I2H
Ignition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . by electric spark
Fuel/ inlet gauge pressure . . . . . . . . . . . . . . . . . . natural gas / 2 kPa, propane / 3.7 kPa
Output stage I / II - ZP (kW) . . . . . 49 / 65 . . . . . . . 59 / 85
70 / 99
91 / 130
105 / 150
Output stage I / II - P(kW) . . . . . . . - / 55 . . . . . . . . . . - . . . . . . . . . . - . . . . . . . . . . - . . . . . . . . . . . . -
Input stage I / II - ZP (kW) . . . . 53,5 / 70,6 . . . . . 64 / 92,4 . . . 75,5 / 107,6 . . . 98,4 / 141 . . . . 113,5 / 163
Input stage I / II – P (kW) . . . . . . .- / 59,8 . . . . . . . . . - . . . . . . . . . . - . . . . . . . . . . - . . . . . . . . . . . . -
Efficiency ZP / P (%) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 / 92
Consumption
Natural gas (cu.m / h) . . . . . . . . . 5,6 / 7,5 . . . . . . 6,8 / 9,8 . . . . . 8,1 / 11,3 . . . . 10,4 / 15 . . . . 12,2 / 17,2
Propane (kg/h) . . . . . . . . . . . . . . . . 6,1 . . . . . . . . . . . - . . . . . . . . . . . - . . . . . . . . . . - . . . . . . . . . . . . -
Burner jet diameter (mm)
Natural gas / Propane . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2,6 / 1,6
Number of burner tubes (pieces) . . . 7 . . . . . . . . . . . . 9 . . . . . . . . . 11 . . . . . . . . . 14 . . . . . . . . . . . 16
Volume of water in the heating body (l)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 27,7 . . . . . . . . . 34,3 . . . . . . . . 40,9 . . . . . . . . 50,8 . . . . . . . . . 57,4
Max. operating temperature (°C) . . . . . . . . . . . . . . . . . . 85 (80°C for open systems)
Max. operating gauge pressure VV (bar) . . . . . . . . . . . . . . . . . . . . . . 4
Min. operating gauge pressure (bar) . . . . . . . . . . . . . . . . . . . . . . . . . 0,3
Test water gauge pressure (bar) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1/N/PE AC 230 V, 50 Hz/TN-S
Electric input (W) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Electric protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP 41
Noise level (dB) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . do 55
Removal of combustion gases
Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .through chimney
Flue diameter (mm) . . . . . . . . . . . . 180 . . . . . . . . . . 200 . . . . . . . . . 220 . . . . . . . . . 250 . . . . . . . . . . 250
Minimum chimney thrust (mbar) . . . . . . . . . . . . . . . . . . . . . . . .0,025 / 2,5 Pa
TTemperature of combustion fumes at max. output ZP / P(°C) . 125 / 100
NO
X
class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Class V
Combustion fumes flow in weight terms at min./max. output
Natural gas (g/s) . . . . . . . . . . . . . 44 / 46,3 . . . . . . 53 / 60,5 . . . . . 63 / 70,5 . . . . . 81 / 92,6 . . . . . . 95 / 107
Propane (g/s) . . . . . . . . . . . . . . . .- / 45,7 . . . . . . . . . - . . . . . . . . . . . - . . . . . . . . . . . .- . . . . . . . . . . . . -
Connection dimensions
Gas / heating water connection . . . . . . . . . . . . . . . . . . . . . . . . . G1" / G6/4"
Boiler width (mm) . . . . . . . . . . . . . . 850 . . . . . . . . . 1010 . . . . . . . 1170 . . . . . . . . 1410 . . . . . . . . . 1570
Boiler height / depth (mm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1195 / 960
Boiler weight (kg) . . . . . . . . . . . . . . 317 . . . . . . . . . . 369 . . . . . . . . 421 . . . . . . . . . 499 . . . . . . . . . 550
These instructions are intended for specialised service only, and together
with Operating Instructions and Service Book provide technical guidelines
for installing, setting up and maintaining the boiler.