  • Page 1

    1 7047-910 october 14, 2013 51-i acc wood insert automatic combustion control (acc) model(s): 5100 acc hot surfaces! Glass and other surfaces are hot during operation and cool down. Hot glass will cause burns. • do not touch glass until it is cooled • never allow children to touch glass • keep child...

  • Page 2

    2 7047-910 october 14, 2013 5100 i-acc table of contents safety alert key: • danger!Indicates a hazardous situation which, if not avoided will result in death or serious injury. • warning! Indicates a hazardous situation which, if not avoided may result in death or serious injury. • caution!Indicate...

  • Page 3

    October 14, 2013 7047-910 3 5100 i-acc model: 5100-i (acc) insert laboratory: intertek report no: 100323198prt-001a type: solidfueltype,listedroomheater standard: ul1482 and ulc s628-93 and (um)84-hud,mobilehome approved. Thequadra-fire5100woodinsert(acc)meetstheu.S.Environ- mental protection agency...

  • Page 4: Install Guide

    4 7047-910 october 14, 2013 5100 i-acc install guide 2 getting started a. Design and installation considerations beforeinstalling,determinethefollowing: • typeofchimneyconnectortobeused · single wall, 6 inch (152mm) diameter, stainless steel, or · double wall, 6 inch (152mm) diameter, stainless stee...

  • Page 5

    October 14, 2013 7047-910 5 5100 i-acc c. Negative pressure negative pressure results from the imbalance of air avail- able for the appliance to operate properly. It can be stron- gest in lower levels of the house. Causesinclude: • exhaustfans(kitchen,bath,etc.) • rangehoods • combustionairrequireme...

  • Page 6

    6 7047-910 october 14, 2013 5100 i-acc attention installer: follow this standard work checklist thisstandardworkchecklististobeusedbytheinstallerinconjunctionwith,notinsteadof,theinstructionscontainedinthisinstallationmanual. Customer: date installed: lot/address: location of fireplace: installer: d...

  • Page 7

    October 14, 2013 7047-910 7 5100 i-acc figure 7.1 top view figure 7.2 front view figure 7.3 - side view 37-7/16 in. (951mm) a b 29-1/16 in. (738mm) 25-1/2 in. (648mm) 12-3/8 in. (314mm) 17-9/16 in. (446mm) 13-1/16 in. (332mm) 26-11/16 in. (678mm) 9-1/8 in. (232mm) 21-3/16 in. (538mm) 20-3/4 in. (528...

  • Page 8

    8 7047-910 october 14, 2013 5100 i-acc note: clearances may only be reduced by means approved by the regulatory authority having jurisdiction fire risk. • complywithallminimumclearancesto combustiblesasspecified. • failuretocomplymaycausehousefire. Warning incanadaafulllength6inch(152mm)s635flueline...

  • Page 9

    October 14, 2013 7047-910 9 5100 i-acc recommended location marginal location location not recommended recommended location location not recommended multi-level roofs windward leeward outside termination cap figure 9.1 d.Chimneyterminationrequirements follow manufacturer’s instructions for clearance...

  • Page 10

    10 7047-910 october 14, 2013 5100 i-acc 3 ft. (91cm) minimum less than 10 ft. (305cm) 2 ft. (61cm) 3 ft. (91cm) minimum 10 ft. (305cm) to nearest roofline 2 ft. (61cm) pitched roof figure 10.1 pitched roof figure 10.2 flat roof 10 ft. (305cm) or more 3 ft. (91cm) minimum less than 10 ft. (305cm) 2 f...

  • Page 11

    October 14, 2013 7047-910 11 5100 i-acc 4 chimney systems d. Masonry chimney •mustmeetminimumstandardsofnfpa211. •musthaveatleast5/8inch(16mm)fireclayliningjoined with refractory cement. (installations into a clay flue without a stainless steel liner may reduce draw which affects performance, will c...

  • Page 12

    12 7047-910 october 14, 2013 5100 i-acc ul 1777 insulated stainless steel liner or other approved lining system follow manufacturer’s instructions on insulation and support for zero or other non-code clearances, follow approved liner manufacturer’s specific insulation requirements: different clearan...

  • Page 13

    October 14, 2013 7047-910 13 5100 i-acc figure 13.1 f. Prefabricated metal chimney thechimneycanbeneworexisting,masonryorprefabricated andmustmeetthefollowingminimumrequirements: •must be minimum 6 inch (152mm) inside diameter of hightemperaturechimneylistedtoul103ht(2100 o f) or ulc s628. •mustusec...

  • Page 14

    14 7047-910 october 14, 2013 5100 i-acc inches millimeters minimumwidthofcavityopening-front 29-1/16 738 minimumwidthofcavityopening-rear 25-1/2 648 minimumheight 20-3/4 528 minimum depth from front to rear 17-9/16 446 damper smokeshelforbaffle ember catches fire grate viewingscreen/curtain doors th...

  • Page 15

    October 14, 2013 7047-910 15 5100 i-acc ovalizing round stainless steel liners to accommodate the linerpassingthroughthedamperregionofafireplaceisan allowable and acceptable practice. Ensure that the ovalization is minimized to the extent requiredtofitthroughthedamper. J. Ovalizing round stainless s...

  • Page 16

    16 7047-910 october 14, 2013 5100 i-acc figure 16.1 optional flex adapter termination cap appliance cover plate (discard) remove 4 bolts on blower housing (both sides)and remove housing remove 2 screws and secure outside cover plate to the back side of the blower housing (included in component pack)...

  • Page 17

    October 14, 2013 7047-910 17 5100 i-acc flue collar stove pipe/liner gasket figure 17.1 figure 17.2 figure 17.3 figure 17.4 cast iron flue located on appliance drill through all 8 countersunk locations once distance is established, drill holes and secure both chambers together. Figure 17.5 b. Securi...

  • Page 18

    18 7047-910 october 14, 2013 5100 i-acc corner brackets figure18.4 figure18.3 secure 2 side surrounds to top surround figure18.5 surround attach points stove top remove 2 screws from both sides. Adjust the legs up or down to level appliance. Figure18.1 attachment bar chimney mounting bar 5/16 nuts a...

  • Page 19

    October 14, 2013 7047-910 19 5100 i-acc figure 19.1 figure 19.2 figure 19.3 remove ground terminal remove strain relief g. Blower cord installation on left side theblowercordisshippedtobeinstalledontherightside of the appliance. You may relocate the cord so it is on the leftside.Youwillneedtoremovet...

  • Page 20

    20 7047-910 october 14, 2013 5100 i-acc figure 20.1 figure 20.2 remove control plate remove strain relief disconnect wires to thesnap disc figure 20.3 figure 20.4 place harness under tabs figure 20.5 figure 20.6.

  • Page 21

    October 14, 2013 7047-910 21 5100 i-acc double-sided tape double-sided tape screws are circled exploded view of scissors figure 21.1 thermal protection decorative tile may be installed install front trim last. Corners overlap side trim pieces expand scissors to desired height cut top edge of trim, n...

  • Page 22

    22 7047-910 october 14, 2013 5100 i-acc figure 22.1 spark arestor cap roof flashing storm collar joist shield/firestop double wall connector pipe 8. Burn wood only. Other types of fuels may generate poisonous gases (e.G., carbon monoxide). 9. If unit burns poorly while an exhaust blower is on in hom...

  • Page 23: 51I- Acc-Bk

    October 14, 2013 7047-910 23 5100 i-acc service parts r 51i- acc-bk beginning manufacturing date: july 2011 ending manufacturing date: active important: this is dated information . Parts must be ordered from a dealer or distributor. Hearth and home technologies does not sell directly to consumers . ...

  • Page 24

    24 7047-910 october 14, 2013 hearth & home technologies 1445 north highway colville, wa 99114 division of hni industries we recommend that you record the following pertinent information for your heating appliance. Date purchased/installed: serial number: location on appliance: dealership purchased f...