Sentrol ZX400 Installation Manual - Specifications and Features
25
Control Board
•
Six (6) two-wire zones, each supervised with a
1500 Ohm end-of-line resistor. “2 in 1” Zon-
ing™ provides twelve (12) fully programmable
zones with 1500 and 825 Ohm resistors. Sys-
tem expansion to 28 fully programmable zones
via Zone Expander Module, ZXEXP.
•
On/Off power switch.
•
One assignable high current alarm output. (Su-
pervised Bell Output).
•
One programmable low current output (40 mA).
•
Fast zone loop response time: 80 msec (zones
1 - 6), 20 msec (zones 7 - 12).
•
Dedicated two-wire smoke detector zones on
control (zone 30) and zone expander (zone 29).
•
Three (3) Control Station activated panic zones.
•
Nominal current drain for control board only
126 - 154 mA.
•
Watchdog microprocessor monitoring.
•
Superior six (6) stage lightning/transient protec-
tion.
•
One switched negative output (100 mA).
•
Expandable to twenty-one (21) programmable
low current outputs via two output driver mod-
ules, and/or a zone expander.
•
Continuous battery monitoring.
•
Low voltage detection monitoring @ 11.3 volts
threshold.
•
Automatic system shutdown if voltage falls be-
low 9.8V.
•
Operating temperature range inside the enclo-
sure: 32
˚
F to 122
˚
F (0
˚
C to +50
˚
C).
•
Two and four-wire smoke zones available.
•
Control Station Programmable.
•
Upload/Download via RPM/2 Pro.
•
Loop response time: 320 msec (general purpose
hardwired zones), 1600 msec (two-wire smoke
zones).
Power Supply
•
Fully regulated 13.8 volt 900 mA supply avail-
able with a 16.5 VAC 35 VA transformer.
•
Optional 16.5 VAC 20 VA transformer provides
450 mA power (not UL Listed).
•
Reverse polarity protection on battery inputs.
•
Float charging circuit: 13.8 volts DC.
SPECIFICATIONS AND FEATURES
Specifications And Features
Recommended Battery
•
Rechargeable 12 VDC 7 Ah sealed lead acid. Use
two (2) batteries to meet CSFM and Household
Fire requirement of 24-hour standby at 450 mA.
•
Rechargeable 12 VDC 17.2 Ah sealed lead acid.
Use one (1) battery to meet CSFM requirement
of 24 hours of standby at 450 mA.
Recommended Transformer
•
UL Listed Class II plug-in; 16.5 VAC 35 VA sec-
ondary; 120 V 60 Hz primary connected to 24-
hour unswitched outlet.
•
Optional UL Listed Class II plug-in 16.5 VAC 20
VA secondary, 120 V 60 Hz primary connected
to 24-hour unswitched outlet.
Enclosure
•
Twenty (20) gauge metal cabinet with knock-
out for optional cam lock. Dimensions: 9"W x
10"H x 2.875"D (228.6 mm x 254 mm x 73.02
mm).
•
Optional EX1414 20 gauge locking metal cabi-
net with two keys. Dimensions 14"W x 14"H x
3.5"D (356 mm x 356 mm x 89 mm).
•
TC1100 Tamper Resistant Enclosure: extra high
security cover (uses EX1414 option).
Digital Communicator
•
DTMF Touchtone™ or Rotary (pulse) dialing.
Rotary speed: 10pps, (selectable U.S. style 60%
break, 40% make or International style 66%
break, 33% make).
•
Ringer equivalence: 0.0B.
•
Transmission formats include: Contact ID, 20
and 40 baud Pulse Formats (3/1, 4/1, 4/2, Hexa-
decimal Reporting), Non-Telco Contact ID,
Pager.
•
Reports to most major Central Station receivers.
•
Primary phone number can have up to 20 digits.
•
Secondary phone number can have up to 20
digits.