Schematic for wiring solar inverters:
The jumper-switch has to be on “PVI-
PVIgo” when the inverter and the current
sensors are connected. In case of inverter
connection only the jumper hast to stay at “PVI”.
4.4.7 D0 digital output
The digital output may be used as an alarm
output to trigger signal transmitters, or as a
pulse output for the connection of a display.
To configure this function you must connect to
KACO-proLOG and make the necessary
adjustments via the browser (Admin Monitoring
-> switch output). The output has been
designed as an optocoupler output (make contact); so
external voltage must be applied as necessary. The
max. load is 50 mA.
Connecting a display to D0
Connecting a signal transmitter to D0
4.4.8 Analog / digital inputs
destroy the sen
The device is equipped with 4 (XL) or,
respectively, 1 (M, L) analog inputs,
which are adjusted for voltage
measurements ranging from 0..10V.
In addition, direct connection of a PT
1000 temperature sensor is enabled. The device has to
be configured accordingly (also please refer to “6.4
PVIweb optional).
KACO-proLOG
RS 485
B A
INV 3
INV 2
INV 1
Voltages greater than 12VDC or reversed poles can
se input!
4 (XL) or, respectively, 1 (M, L) can be
used to pick up digital counter inputs
(max. frequency: 14 Hz). This will
require an interface according to S0
specification.
External voltages greater than 24 VDC
or reversed poles can destroy the
sense input. The 24VDC supply is
available starting from the D0+
terminal.
Connection of an insolation (solar radiation)
sensor and energy meter:
Input AI1 has been pre-configured for the connection of
an insolation sensor. Digital input DI1 has been pre-
configured for the connection of a grid-feeding meter.
KACO-proLOG
24V
+ -
+ -
DI1
+ -
AI1
Signal
GND
24V
+
Meter
Insolation
sensor
Si-12TC
Energy
meter
D0
+ -
+ -
KACO-proLOG
Display
Pulse input
KACO-proLOG
+ -
D0
+ -
24V
+ -
Signal transmitter
KACO SOLAR INC.
6
Operator’s Instructions KACO-proLOG