NautiCharger PM-0600H User Manual

Summary of PM-0600H

  • Page 1

    High frequency pure sine wave inverter user manual model: pm-0600h pm-1000h pm-1500h pm-2000h pm-3000h.

  • Page 2: Content

    -1- content safety instructions a. General safety precautions --------------------------------------------- 1 b. Explosive gas precautions ----------------------------------------------1 c. Precautions when working with batteries ------------------------ 1 features ----------------------------------...

  • Page 3: Safety Instructions

    -2- safety instructions a. General safety precautions a-1. Do not expose the inverter to rain, snow, spray, bilge or dust. To reduce risk of hazard, do not cover or obstruct the ventilation openings. Do not install the inverter in a zero-clearance compartment. Overheating may result. A-2.To avoids a...

  • Page 4: Features

    -3- c-1. Never smokes or allow a spark or flame in vicinity of battery or engine. C-2. Do not drop a metal tool on the battery. The resulting spark or short-circuit on the battery or other electrical part may cause an explosion. C-3. Remove personal metal items such as rings, bracelets, necklaces, a...

  • Page 5

    -4-.

  • Page 6

    -5- e. Name and main function: e-1. Front view: e-1-1. On / off switch: power on/off switch, leave in the off position during installation. E-1-2. Green power: power energy saving enable. Over volt: over voltage protection. Under volt: under voltage protection. Over temp: over temperature protection...

  • Page 7: F. Rear View

    -6- f. Rear view f-1. Ventilation window : do not obstruct, allow at least 1 inch for air flow. F-2. Battery terminals : connect to 12v / 24v / 48v battery or other 12v / 24v / 48v power source. [ + ] is positive, [ - ] is negative. Reverse polarity connection will blow internal fuse and may damage ...

  • Page 8: Warning !

    -7- g. Quick hook – up and testing: if you would like to quick hook-up the power inverter and check its performance before going ahead with your installation, please follow these guidelines: g-1. Unpack and inspect the power inverter, check to see that the power switch in the off position. G-2. Conn...

  • Page 9: H. Installation:

    -8- g-5. Set the power switch to the on position. Check the meters and indicators on the front panel of the inverter. The voltage bar graph indicate depending on the voltage of the power source. If does not, check your power source and the connections to inverter. The other indicators should be off....

  • Page 10

    -9- h-1-5. Dust-free –do not install the inverter in a dusty environment where either dust, wood particles or other filings/shavings are present. These can pulled into the unit when the cooling fan is operating. H-1-6. Close to battery/batteries – avoid excessive cable lengths but do not install the...

  • Page 11: Warning!

    -10- from the utility is tied to ground at the ac breaker panel. For models configured with a transfer relay, when ac utility power is present and the inverter is in bypass mode, this connection (neutral of the inverter’s ac output to input safety ground )is not present so that the utility neutral i...

  • Page 12: I. Operation:

    -11- input terminals on the inverter. Your cables should be as short as possible (ideally, less than 10 feet / 3 meters) and large enough to handle the required current, in accordance with the electrical codes or regulations applicable to your installation. Cables that are not an adequate gauge (too...

  • Page 13

    -12- 48v models. From 600watts up to 3000watts. I-2. Battery voltage indicator : the battery voltage bar graph indicates the voltage at the input terminals of the power inverter at low input current, this voltage is very close to the battery voltage. At high input current, this voltage will be lower...

  • Page 14: J. Operating Limits:

    -13- i-6. Over temp indicator : the over temp indicator indicates that the power inverter has shut itself down because it has become overheated. The power inverter may overheat because it has been operated at power levels above its rating, or because it has been installed in a location which does no...

  • Page 15: K. Trouble Shooting:

    -14- connections are good and the battery is charged, but the voltage still drops below 11 volts, you may need to use a larger battery. K. Trouble shooting: k-1. Common problems television interference : operation of the power inverter can interfere with television reception on some channels. If thi...

  • Page 16

    -15- problem and symptoms possible cause solution low output voltage using average reading use true rms 110v : 95-105vac,220v voltmeter and cable. 220v : 190-210vac see page 7 point 6-7. Of manual load led bar flash. Overload reduce load. No output voltage. Low input voltage. Recharge battery, and v...

  • Page 17: L. Maintenance

    -16- l. Maintenance very little maintenance is required to keep your inverter operating properly. You should clean the exterior of the unit periodically with a damp cloth to regent accumulation of dust and dirt. At the same time, tighten the screws on the dc input terminals..

  • Page 18: Appendix  A

    -17- appendix a a-1. Dip switch (110v) s1 s2 function s3 s4 output voltage s5 out frequency off off dc/ac out mode. Off off 120v off 60hz off on dc/ac +green power mode. On off 115v on 50hz on off ups mode. Off on 110v on on ups mode +delay mode +green power. On on 100v dip switch (220v) s1 s2 funct...

  • Page 19

    -18- a-2 ndc-ac structure schema : 1. Code explanation: (a) dc/ac out mode : no matter shore power has/ hasn’t the power the ac output is supply by dc/ac (so the ac transfer switch is on) ( no green power function). (b) dc/ac out mode + green power mode : ac output power supply by dc/ac ( ac transfe...

  • Page 20

    -19- also treat as power unusually so it will automatically transfer to dc/ac output this 15% range can be setting from the remote controller (d) ups mode + delay mode + green power : ups mode + delay mode : same as ups mode the only different is when ac transfer switch working it won’t complete in ...