NautiCharger PM-0600H User Manual - J. Operating Limits:
-13-
I-6. Over temp indicator :
The over temp indicator indicates that the power inverter has shut
itself down because it has become overheated. The power
inverter may overheat because it has been operated at power
levels above its rating, or because it has been installed in a
location which does not allow it to dissipate heat properly. The
power inverter will restart automatically once it has cooled off.
I-7.Overload indicator :
The overload indicator indicates that the power inverter has shut
itself down Because its output circuit has been short circuited or
drastically overloaded.
Switch the ON/OFF switch to OFF, correct the fault condition, and
then switch the ON/OFF switch back to ON.
J. Operating limits:
J-1. Power output:
The inverter will operate most AC loads within its power rating.
When deeming whether a microwave over can be operated by
the inverter, remember that the power commonly advertised for
microwave ovens is the cooking power (the power delivered to
the food) not the power actually consumed by the microwave
oven. The microwave over will consume 40% to 100% more than
its advertised cooking power. Check the rating sticker on the
back of the over to determine its actual power draw.
The Power inverter may not be able to start some of this motor
even though their rated current draw is within the power inverter.
If motor refuse to start, observe the battery voltage indicator while
trying to Start the motor. If the battery voltage indicator drops
below 11 volts while inverter is attempting to start the motor, this
may be why the motor won’t start. Make sure that the battery
connections are good and that the battery is fully charged. If the