Pacific Energy NEO 1.6 Installation And Operating Instructions Manual - Chimney and Connector
WARNING: INSTALL CHIMNEY AND ALL COMPONENTS OF CHIMNEY
SYSTEM ACCORDING TO CHIMNEY MANUFACTURER’S INSTRUCTIONS.
Connect to a listed chimney complying with the requirements of AS/NZS2918/2001 and a chimney suitable for use with solid fuel
that is lined and in good condition and meets local building codes. The chimney flue size should be the same as the stove outlet
for optimal performance. Reducing or increasing the flue size may adversely affect stove performance. Chimney flue exit is to be
minimum 100 cm above roof and 60 cm above highest projection within 300 cm. The installation must meet all local codes. Do not
connect this unit to a chimney flue serving another appliance. Minimum system height is 460 cm (measured from base of appliance).
Installation Procedure -Residential
1. Install all components to the chimney manufacturer's installation requirements. (Outside combustion air may be required,
consult local building codes. See Combustion Air section on page 11.)
2. Installed with the crimped or male ends pointing down. This will carry any liquid creosote or condensation back into the stove.
3. If a roof or ceiling support is used in the installation, you will find the chimney manufacturer's complete instructions packed with
the roof support.
4. To start installing smoke pipe (chimney connector), slip crimped edge of the pipe inside the stove collar. Use holes provided in
collar to secure pipe with three screws.
5. Install the remaining lengths of pipe, one on top of the other, to the finished height of the chimney connector and secure to each
other.
Chimney and Connector
300 cm
100 cm min.
if clear within
300 cm of flue
more than 300 cm
300 cm
or less
60 cm min
300 cm
increase as necessary
until nothing within
300 cm of flue top
Any nearby structure
300 cm
increase
from 100 cm
min.until
clear within
300 cm of
flue top
more than 300 cm
300 cm
or less
60 cm min
Figure 6. Neo 1.6 Chimney and connector