The power rating of inverters is specifi ed as follows:
• MaximumContinuousRunningPowerRating
• SurgePowerRatingtoaccommodatehigh,shortdurationsurgeofpowerrequired
during start up of certain AC appliances and devices.
Please read details of the above two types of power ratings in Section 2.1 under
“DEFINITIONS”
i
INFO
The manufacturers’ specifi cation for power rating of AC appliances and devices
indicatesonlytheMaximumContinuousRunningPowerRating.Thehigh,
short duration surge of power required during start up of some specifi c types
ofdeviceshastobedeterminedbyactualtestingorbycheckingwiththe
manufacturer. This may not be possible in all cases and hence, can be guessed
at best, based on some general Rules of Thumb.
Table 2.1 provides a list of some common AC appliances / devices that require high, short
duration surge of power during start up. An “Inverter Sizing factor” has been recom-
mendedagainsteachwhichisaMultiplicationFactortobeappliedtotheMaximum
Continuous Running Power Rating (Active Power Rating in Watts) of the AC appliance
/devicetoarriveattheMaximumContinuousRunningPowerRatingoftheinverter
(MultiplytheMaximumContinuousRunningPowerRating(ActivePowerRatingin
Watts)oftheappliance/devicebyrecommendedSizingFactortoarriveattheMaxi-
mum Continuous Running Power Rating of the inverter.
TABLE 2.1: INVERTER SIZING FACTOR
Type of Device or Appliance
Inverter
Sizing Factor
(See note 1)
Air Conditioner / Refrigerator / freezer (Compressor based)
5
Air Compressor
4
Sump Pump / Well Pump / Submersible Pump
3
Dishwasher/ClothesWasher
3
Microwave(whereratedoutputpoweristhecookingpower)
2
furnace fan
3
Industrial Motor
3
PortableKerosene/DieselFuelHeater
3
CircularSaw/BenchGrinder
3
Incandescent/Halogen/QuartzLamps
3
LaserPrinter/OtherDevicesusingInfraredQuartzHalogenHeaters
4
Switch Mode Power Supplies (SMPS): no Power factor correction
2
PhotographicStrobe/FlashLights
4 (See Note 2)