Samlexpower PST-1500-12 Owner's Manual - Section 8 |
38 | SAMLEX AMERICA INC.
NOTE: for the Reset Button to operate, the inverter has to be in ON condition so that
ACpowerisavailabletotheinternalLineSideoftheGFCI
- Test Button:ThisbuttonisusedtotestiftheGFCIisoperatingnormally.TesttheGFCI
periodically to ensure that it is operating normally.
TheGFCIwilltripduetothefollowingconditions:
- Leakageorgroundfault(Leakageof5to6mA)
- NeutraltoGroundbonding(connection)ontheloadsideoftheGFCI
!
CAUTION!
1.DonotfeedtheoutputfromtheGFCIreceptacletoaPanelBoard/LoadCenter
wheretheNeutralisbondedtotheEarthGround.ThiswilltriptheGFCI.
2.Ifanextensioncordisused,pleaseensurethatthecordis2-PoleGroundingType
8.5.3.1 AC Output Connections for Hardwiring
ForconnectingtheACoutputoftheinvertertoanACDistributionPanelboard/Load
Center,separateconnectionsareavailableforhardwiring.PleaserefertoFig6.1.Com-
partment(13,Fig6.1)containsterminalsforACoutput.Thecompartmentiscoveredby
CoverPlate(12,Fig6.1)withthehelpof4screws.ACoutputconnectionsareasfollows:
Line “L” (15, Fig 6.1) and Neutral “N” (16, Fig 6.1) Terminals.
PleasenotethatLineterminal“L”(15,Fig6.1)oftheACTerminalBlockandtheLine
terminalontheLinesideoftheGFCIareinternallyconnectedtogetheratthePCB.
Similarly,Neutralterminal“N”(16,Fig6.1)ontheACTerminalBlockandtheNeutral
terminalontheLinesideoftheGFCIareinternallyconnectedtogetheratthePCB
• Holediameter:4mm/0.16"
• Setscrew:#6(UNF,40ThreadsperInch)orM3.5(CoarsePitch0.6mm)
AC Ground Terminal (14, Fig 6.1)
• Stud:#6(UNC,32ThreadsPerInch)
Neutral to Chassis Ground Bonding
• Neutral“N”(16,Fig6.1)isbondedtothemetalchassisoftheinverterthroughaloopof
wireconnectingthe“N”terminalontheLinesideoftheGFCItothechassisoftheinverter.
WARNING!
RISK OF ELECTRIC SHOCK. When this unit is installed in vehicles and hard-wiring
connectionisusedtofeedtheACoutputoftheinvertertotheACDistribution
Panelboard/LoadCenterinthevehicle,itistobeensuredthatGroundFault
CircuitInterrupter(s)[GFCI]areinstalledinthevehiclewiringsystemtoprotect
all Branch Circuits.
ThefollowingGFCIshavebeentestedtooperatesatisfactorilyandareacceptable.Other
types may fail to operate properly when connected to this inverter: