installation
8.1 LOCATION OF INSTALLATION
Please ensure that the following requirements are met:
Working Environment: Indoor use.
Cool: Heat is the worst enemy of electronic equipment. Hence, please ensure that the
unit is installed in a cool area that is also protected against heating effects of direct
exposuretothesunortotheheatgeneratedbyotheradjacentheatgeneratingdevices.
Well Ventilated: The unit is cooled by convection and by forced air-cooling by 2 tempera-
turecontrolledfans(behindopenings6,Fig6.1).Thefansdrawcoolairfromair-suction
openingsinthefrontandbottom(17,Fig6.1)anddischargehotairthroughtheexhaust
openingsnexttothefans(6,Fig6.1).Toavoidshutdownoftheinverterduetoover
temperature,donotcoverorblockthesesuction/exhaustopeningsorinstalltheunitin
an area with limited airflow. Keep a minimum clearance of 10” around the unit to provide
adequate ventilation. If installed in an enclosure, openings must be provided in the enclo-
sure,directlyoppositetotheair-suctionandair-exhaustopeningsoftheinverter.
Dry:Thereshouldbenoriskofcondensation,wateroranyotherliquidthatcanenter
or fall on the unit.
Clean: The area should be free of dust and fumes. Ensure that there are no insects or
rodents.Theymayentertheunitandblocktheventilationopeningsorshortcircuitelec-
trical circuits inside the unit.
Protection Against Fire Hazard: The unit is not ignition protected and should not be
locatedunderanycircumstanceinanareathatcontainshighlyflammableliquidslike
gasolineorpropaneasinanenginecompartmentwithgasoline-fueledengines.Donot
keepanyflammable/combustiblematerial(i.e.,paper,cloth,plastic,etc.)neartheunit
thatmaybeignitedbyheat,sparksorflames.
Closeness to the Battery Bank:Locatetheunitasclosetothebatterybankaspossible
topreventexcessivevoltagedropinthebatterycablesandconsequentpowerlossand
reduced efficiency. However, the unit should not be installed in the same compartment
asthebatteries(floodedorwetcell)ormountedwhereitwillbeexposedtocorrosive
acidfumesandflammableOxygenandHydrogengasesproducedwhenthebatteries
are charged. The corrosive fumes will corrode and damage the unit and if the gases are
notventilatedandallowedtocollect,theycouldigniteandcauseanexplosion.
Accessibility:Donotblockaccesstothefrontpanel.Also,allowenoughroomtoaccess
theACreceptaclesandDCwiringterminalsandconnections,astheywillneedtobe
checkedandtightenedperiodically.
Preventing Radio Frequency Interference (RFI): The unit uses high power switching
circuitsthatgenerateRFI.ThisRFIislimitedtotherequiredstandards.Locateanyelec-
tronic equipment susceptible to radio frequency and electromagnetic interference as far
away from the inverter as possible. Read Section 3, “Limiting Electromagnetic Interfer-
ence (EMI)” for additional information.