6-2-8. Low Temp Release
●
AT COOLING MODE
◆
If the temperature of indoor heat exchanger is below -1°C for over 6minutes, the outdoor fan turns off.
◆
If the temperature of indoor heat exchanger increase over 5°C during the first protection function, the first freezing protection
function is released and the outdoor fan turns on.
◆
If the temperature of indoor heat exchanger increase over 0°C during 6 minutes counting, 6 minutes counter is cleared.
◆
If the temperature of indoor heat exchanger maintains for a minute at -4°C during the 6 minutes counting, switch off the
compressor.
◆
If the compressor is off by Low Temp. Release, 5 minutes release is impossible.
◆
Operating Pattern
Indoor Heat exchanger Temp.(˚C)
5[˚C]
0[˚C]
-1[˚C]
6min
COUNT
ON
6min
COUNT
OFF
6min
COUNT
ON
Low temp.
release
ON
Low temp.
release
OFF
6min
3sec
2sec
ON
ON
OFF
ON
ON
OFF
Setting Fan speed
Setting Fan speed
"LL"
COMP_or
Outdoor FAN
Indoor FAN
*LL = Low FAN speed – 35rpm