Samsung AQ07P8GE Training Manual - page 93
92 | SAMSUNG
8
Troubleshooting for Non Inverter Heat Pump
(12K)
(Cont.)
◆
When the Indoor Unit Fan Does Not Operate. (Initial Diagnosis)
1) Checklist :
(1) Is the indoor unit fan motor properly connected with the connector (CN72)?
(2) Is the AC voltage correct?
(3) Is HALL IC in indoor fan motor properly connected with the connector (CN44)?
(4) Is the running capacitor properly connected with PCB board?
2) Troubleshooting procedure
After unplugging out the power cord should
be reconnected within five seconds.
Does the OPERATION lamp blink?
Does the Solid State Relay(SS71) work
properly?
Is the supply voltage of the fan
motor sufficient?
Test rod location
PCB CN73
Condition
Fan operate
about AC 180V
Normal
voltage
Pin #3 and
Pin #5
YES
YES
YES
YES
NO
NO
NO
Check as in the procedur “NO power parts”
PCB is
out of order.
Refer to replace PCB
module
Replace MFC
Fan motor
should be replaced.
Fan motor
is out of order.
MF-C is out of order
-
Test rod location
+
SS71+
SS71-
12V
Normal
Voltage
Microcomputer is
out of order.
Microcomputer
shoud be replaced
TROUBLESHOOTING