Samsung AQ07P8GE Training Manual - page 80
SAMSUNG | 79
1
TROUBLESHOOTING
8
Troubleshooting for Non Inverter Cooling Only
(7K/9K)
(Cont.)
◆
When the UP/DOWN Louver Moter Does Not Operate. (Initial Diagnosis)
1) Checklist :
(1) Is input voltage normal?
(2) Is the UP/DOWN louver motor properly connected with the connector (CN61)?
2) Troubleshooting procedure
◆
In the mode, When there is no cool air current. Check this first;
(1) Is the set temperature of Remote Control lower than room temperature in Cool mode?
(2) Is the Indoor PCB properly connected with the CN71 connector?
Remove power cord and plug in again in approx. 5 seconds.
Is STD lamp blinking?
Does operation start when swing button of the
remote control unit pushed?
Voltage at pin #57~#60 of micom (ICO4)
change?(Squarewave)
Volatge at pin #16 of IC06 (ULN2003A) and #10~#12 of
IC08 (ULN2003A) change?(Squarewave)
UP/DOWN louver motor is faulty.
Driver IC06/08 (ULN2003A) is faulty.
Micom (IC04) is faulty.
Normal
Check as in the procedure
"No Power parts".
After training on, the Cooling operation
should start in five minutes.
Is the munber #38 of Micom (IC04) DC 5.0 V?
Is the munber checking #11 of IC05 (ULN2003A) LOW?
RY7I or Cable Check.
NO
YES
NO
NO
YES
Normal
Abnormal Micom
Abnormal IC05
PCB should be replaced.
YES
YES
YES
NO
NO
YES
NO
NO
DB98_08187A(1)_57~100 3/27/03 2:24 PM Page 79