    Installation manual integrated bacnet ac drives vacon ® 100 x vacon ® 100 hvac vacon ® 100 flow vacon ® 100 industrial.

  • Page 3

    Vacon • 1 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ table of contents document: dpd00091d version release date: 8.12.16 1. Safety................................................................................................................2 1.1 danger...................

  • Page 4

    1 vacon • 2 safety local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 1. S afety this manual contains clearly marked cautions and warnings that are intended for your personal safety and to avoid any unintentional damage to the product or connected appliances. Please read the in...

  • Page 5

    Safety vacon • 3 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 1 1.2 warnings the ac drive is meant for fixed installations only . Do not perform any measurements when the ac drive is connected to the mains. The earth leakage current of the ac drives exceeds 3.5ma ac. Acco...

  • Page 6

    1 vacon • 4 safety local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 1.3 earthing and earth fault protection the ac drive must always be earthed with an earthing conductor connected to the earthing terminal marked with . The earth leakage current of the drive exceeds 3.5ma ac....

  • Page 7

    Bacnet - general info vacon • 5 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 2 2. Bac net - general info bacnet stands for ‘building automation and control networks’. It is the common name for the communication standard iso 16484-5 which defines the methods and the protoc...

  • Page 8

    3 vacon • 6 bacnet technical data local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3. Bac net technical data 3.1 bacnet ms/tp protocol 3.2 bacnet ip protocol 3.3 acd (address conflict detection) the vacon ® 100 family ac drives implement the acd algorithm (ietf rfc 5227). The...

  • Page 9

    Programming vacon • 7 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 4 4. P rogramming you will find basic information on how to use the control keypad in the application manual of your vacon ® 100 family ac drive. Below you will find some examples of navigation paths to th...

  • Page 10

    4 vacon • 8 programming local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 4.1 bacnet ms/tp parameters and monitoring values table 5. Parameters related with bacnet used through ms/tp code parameter min max default id description p5.8.3.1.1 baud rate 9600 76800 9600 2392 commun...

  • Page 11

    Programming vacon • 9 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 4 4.2 bacnet ip parameters and monitoring values 4.2.1 ethernet common settings 4.2.2 bacnet ip settings table 7. Ethernet common settings code parameter min max default id description p5.9.1.1 ip address ...

  • Page 12

    4 vacon • 10 programming local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ table 9. Monitoring values code parameter min max id description v5.9.3.2.1 fieldbus protocol status initializing inactive 2412 see table 11 v5.9.3.2.2 communication status 0.0 99.999 2413 counter for f...

  • Page 13

    Programming vacon • 11 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 4 4.3 bacnet ms/tp parameter descriptions 4.3.1 bacnet ms/tp parameters p5.8.3.1.1 b aud rate select the communication speed for the network. The default value is 9600 baud. If autobauding is selected, th...

  • Page 14

    4 vacon • 12 programming local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ p5.8.3.1.6 m ax apdu cycle this parameter defines the maximum time in seconds between apdu messages addressed to this node. The apdu messages are application layer messages, for example, 'readparameter'...

  • Page 15

    Programming vacon • 13 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 4 4.4 bacnet ip parameter descriptions 4.4.1 ethernet common settings p5.9.1.1 ip address mode selectable alternatives are dhcp (dynamic host configuration protocol) and fixed . Dhcp protocol gives ip add...

  • Page 16

    4 vacon • 14 programming local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 4.4.2 bacnet ip settings p5.9.3.1.1 i nstance number similar to bacnet ms/tp device object instance number (see chapter 4.3.1). P5.9.3.1.2 bac net p ort n umber the udp port for the bacnet ip communicat...

  • Page 17

    Programming vacon • 15 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 4 4.4.3 bacnet ip monitoring values v5.9.3.2.1 f ieldbus protocol status fieldbus protocol status tells the status of the protocol. V5.9.3.2.2 c ommunication status the communication status shows how many...

  • Page 18

    5 vacon • 16 installation local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 5. I nstallation 5.1 vacon ® 100 family ac drive 1 open the cover of the ac drive. The relay outputs and other i/o-terminals may have a dangerous control voltage present even when the ac drive is disco...

  • Page 19

    Installation vacon • 17 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 5 5.1.1 prepare for use through ethernet 3 connect the ethernet cable (see specification in chapter 3.2) to its terminal as shown in figure below. Ethernet cable 9316.Emf.

  • Page 20

    5 vacon • 18 installation local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 4 protection class ip21: cut free the opening on the ac drive cover for the ether- net cable. Protection class ip54: cut the rubber grommets open to slide the cables through. Should the grommets fold i...

  • Page 21

    Installation vacon • 19 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 5 5 remount the ac drive cover. Note! When planning the cable runs, remember to keep the distance between the ethernet cable and the motor cable at a minimum of 30 cm . Ip54 9265.Emf ip21 ethernet cable.

  • Page 22

    5 vacon • 20 installation local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 5.1.2 prepare for use through rs485 1 strip about 15 mm of the rs485 cable (see specification in chapter 3.1) and cut off the grey cable shield. Remember to do this for both bus cables (except for the ...

  • Page 23

    Installation vacon • 21 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 5 2 then connect the cable to its appropriate terminals on vacon ® 100 family ac drive standard terminal block, terminals a and b (a = negative, b = positive). See figure below. 3 using the cable clamp i...

  • Page 24

    5 vacon • 22 installation local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 4 if vacon ® 100 family ac drive is the last device on the bus , the bus termination must be set. Locate the dip switches to the right of the control keypad of the drive and turn the switch for the rs4...

  • Page 25

    Installation vacon • 23 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 5 7 the bus termination must be set for the first and the last device of the fieldbus line. See picture below. See also step 3 on page 22. Fieldbus cable = bus termination termination activated terminati...

  • Page 26

    5 vacon • 24 installation local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 5.2 installation in vacon ® 100 x the ac drive can be connected to fieldbus either through rs485 or ethernet. The connection for rs485 is on the standard i/o terminals (a and b) and the connection for ...

  • Page 27

    Installation vacon • 25 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 5 5.2.2 prepare for use through rs485 1 strip about 15 mm of the rs485 cable (see specification in chapter 3.1) and cut off the grey cable shield. Remember to do this for both bus cables (except for the ...

  • Page 28

    5 vacon • 26 installation local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 4 if vacon ® 100 x ac drive is the last device on the bus , the bus termination must be set. Locate the dip switches to the top of the control unit (see figure below). Turn the right most switch to pos...

  • Page 29

    Communications vacon • 27 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 6 6. C ommunications 6.1 device object device object provides information about device and its configuration. Note that the device object "object_name" property corresponds to the ac drive’s “drive nam...

  • Page 30

    6 vacon • 28 communications local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ *. Only with commandable values 6.2.1 binary value object active_cov_subscriptions x event_state x x out_of_service x x present_value x x priority_array x * x * relinquish_default x * x * status_flag...

  • Page 31

    Communications vacon • 29 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 6 note! Present value access types: r = read-only, w = writeable, c = commandable. Commandable values support priority arrays & relinquish defaults. 6.2.2 analogue value object bv18 stop by coast stop ...

  • Page 32

    6 vacon • 30 communications local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 1) ansi/ieee-754 floating point. Binary coding can be done only if the value has no decimals. 2) map only analog data to these objects. If binary coded data is mapped into these objects, the data may...

  • Page 33

    Communications vacon • 31 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 6 high and low limits for the objects are defined in the application. See corresponding application for exact limits. 6.3 control word bits 6.4 status word bits 6.5 cov functionality it is possible to ...

  • Page 34

    6 vacon • 32 communications local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 6.6 processdata mapping in drive application the drive application allows you to choose freely which data is mapped into processdata out objects. See the drive appllication 'fieldbus datamap' paramet...

  • Page 35

    Fault tracing vacon • 33 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 7 7. F ault tracing when an unusual operating condition is detected by the ac drive control diagnostics, the drive initiates a notification visible, for example, on the keypad. The keypad will show the ...

  • Page 36

    7 vacon • 34 fault tracing local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 7.2 other fault conditions the following fault tracing diagram will help you to locate and fix some of the most usual problems. If the problem persists contact your local distributor. Figure 3. Fault ...

  • Page 37

    Fault tracing vacon • 35 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 7 figure 4. Fault tracing diagram for bacnet ip dr iv e d o e s n o t st a rt fr o m th e b u s ch ec k c o m m u n i- ca ti o n st at u s (p ar . Co u n te r d o e s n o t ru n co u n te r fo r ba d fr...

  • Page 38

    8 vacon • 36 quick setup local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 8. Q uick setup following these instructions, you can easily and fast set up your bacnet bus for use. 1 parametrize bacnet functionality as described in chapter 4. “programming”. 2 make these settings i...

  • Page 39

    Annex - protocol implementation conformance statement vacon • 37 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 9 9. A nnex - p rotocol implementation conformance statement protocol implementation conformance statement (normative) (this annex is part of this standard and is...

  • Page 40

    9 vacon • 38 annex - protocol implementation conformance statement local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ the analog values that are commandable contain the priority array and relinquish default properties. All analog values that are not commandable become writable ...

  • Page 41

    Annex - protocol implementation conformance statement vacon • 39 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 9 analog value object table 21: analog value object - commandable object property readable writable commandable object-identifier x object-name x object-type x pr...

  • Page 42

    9 vacon • 40 annex - protocol implementation conformance statement local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ binary value object table 23: binary value object - commandable object property readable writable commandable object-identifier x object-name x object-type x pr...

  • Page 43

    Annex - protocol implementation conformance statement vacon • 41 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 9 data link layer options: ms/tp master (clause 9), baud rate(s): 9600,19200,34800, 76800 (supports autobaud detection) bacnet ip, (annex j), foreign device devic...

  • Page 44

    Document id: dpd00091d rev. D sales code: doc-insbacnet+dluk vacon ltd member of the danfoss group runsorintie 7 65380 vaasa finland www.Danfoss.Com.