Vega VEGABAR 54 Product Information - page 6
2
Type overview
VEGABAR 51
VEGABAR 52
VEGABAR 52 - climate compensated
Measuring cell:
CERTEC
®
/DMS
CERTEC
®
CERTEC
®
Diaphragm:
Metal
Ceramic
Ceramic
Media:
gases, vapours and liquids, also
aggressive ones, at high
temperatures
Gases, vapours and liquids
Gases, vapours and liquids
Process fitting:
Thread from ½", flanges from DN 20,
boltings, isolating diaphragms each
from DN 25
Manometer connection G½ A or
M
20 x 1.5 according to EN 837,
connection G½ A inner G¼ A, ½ NPT
inner ¼ NPT
Manometer connection G½ A or
M
20 x 1.5 according to EN 837,
connection G½ A inner G¼ A, ½ NPT
inner ¼ NPT
Material process fitting:
316L, Hastelloy C276
316L, Hastelloy C276, PVDF
316L, Hastelloy C276, PVDF
Material diaphragm:
316L, Hastelloy C276, Hastelloy C2,
Tantalum, Titanium, PTFE on 316Ti,
gold-coating on 316L
Ceramic
Ceramic
Measuring range:
-1 … 400 bar (-14.5 … 5802 psig)
-1 … 72 bar (-14.5 … 1044 psig)
-1 … 72 bar (-14.5 … 1044 psig)
Smallest measuring range: 0.4 bar (5.802 psig)
0.1 bar (1.45 psig)
0.2 bar (3 psig)
Process temperature:
-40 … +400 °C (-40 … +752 °F)
-40 … +120 °C (-40 … +248 °F)
-40 … +120 °C (-40 … +248 °F)
Deviation:
<
0.2 %
<
0.2 %, < 0.1 %
<
(0.05 + 0.025 x TD) %
Signal output:
4 … 20 mA/HART, Profibus PA,
Foundation Fieldbus
4 … 20 mA/HART, Profibus PA,
Foundation Fieldbus
4 … 20 mA/HART, Profibus PA,
Foundation Fieldbus
Connection:
Housing with terminals, IP 66/IP 67
Housing with terminals, IP 66/IP 67
Housing with terminals, IP 66/IP 67
Adjustment/Indication:
PLICSCOM
PLICSCOM
PLICSCOM
Remote adjustment/
indication:
VEGADIS
61
VEGADIS
61
VEGADIS
61
Functional safety:
up to SIL3
up to SIL3
--
Type overview
6
Process pressure/Hydrostatic – Pressure measurement
29234
-EN
-081013