Vega VEGAPULS 61 Operating Instructions Manual

Manual is about: Radar sensor for continuous level measurement of liquids

Summary of VEGAPULS 61

  • Page 1

    Operating instructions radar sensor for continuous level measurement of liquids vegapuls 61 modbus and levelmaster protocol document id: 41361.

  • Page 2: Contents

    2 contents vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 contents 1 about this document 1.1 function ........................................................................................................................... 4 1.2 target group ...........................................

  • Page 3

    3 contents vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 8.1 maintenance .................................................................................................................. 59 8.2 measured value and event memory ............................................................

  • Page 4: 1  About This Document

    4 1 about this document vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 1 about this document 1.1 function this operating instructions manual provides all the information you need for mounting, connection and setup as well as important instruc- tionsformaintenanceandfaultrectification....

  • Page 5: 2  For Your Safety

    5 2 for your safety vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 2 for your safety 2.1 authorised personnel all operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator. During work on and wi...

  • Page 6

    6 2 for your safety vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 2.5 ce conformity thedevicefulfillsthelegalrequirementsoftheapplicableecguide- lines.Byaffixingthecemarking,weconfirmsuccessfultestingofthe product. Youcanfindthececertificateofconformityinthedownloadsection of our hom...

  • Page 7

    7 2 for your safety vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 2.8 radio license for usa/canada the instrument is in conformity with part 15 of the fcc regulations. Take note of the following two regulations: • this device may not cause interference, and • this device must accept ...

  • Page 8: 3  Product Description

    8 3 product description vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 3 product description 3.1 configuration thetypelabelcontainsthemostimportantdataforidentificationand use of the instrument: 2 1 15 13 14 12 11 5 3 6 4 7 8 10 9 fig. 1: layout of the type label (example) 1 instrumen...

  • Page 9

    9 3 product description vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 theinstrumentcontainstwodifferentelectronicsinitshousingcham- bers: • the modbus electronics for power supply and communication with the modbus-rtu • the sensor electronics for the actual measuring tasks 2 1 fig. 2...

  • Page 10

    10 3 product description vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 3.2 principle of operation the vegapuls 61 is a radar sensor for continuous level measure- ment of liquids under simple process conditions. Dependentontheapplicationrange,differentversionsareused: • level measurem...

  • Page 11

    11 3 product description vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 • storage and transport temperature see chapter "supplement - technical data - ambient conditions" • relative humidity 20 … 85 % 3.4 accessories and replacement parts the display and adjustment module plicscom is ...

  • Page 12: 4 Mounting

    12 4 mounting vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 4 mounting 4.1 general instructions oninstrumentswiththreadedprocessfitting,thehexagonmustbe tightenedwithasuitablewrench.Fortheproperwrenchsizesee chapter "dimensions". Warning: the housing must not be used to screw the ins...

  • Page 13

    13 4 mounting vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 prior to setup you have to replace these protective caps with ap- proved cable glands or close the openings with suitable blind plugs. 4.2 collaroradapterflange formountingtheinstrumentonasocket,acombicompressionflange fordn...

  • Page 14

    14 4 mounting vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 • single chamber housing – angleofinclination180°,infinitelyvariable – angle of inclination in three steps 0°, 90° and 180° • double chamber housing – angleofinclination90°,infinitelyvariable – angle of inclination in two st...

  • Page 15

    15 4 mounting vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 1 2 fig. 6: position of the polarisation 1 marking with version with plastic horn antenna 2 marking with version with encapsulated antenna system when mounting the sensor, keep a distance of at least 200 mm (7.874 in) to the...

  • Page 16

    16 4 mounting vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 fig. 8: mounting of the radar sensor on vessels with conical bottom donotmounttheinstrumentsinorabovethefillingstream.Makesure thatyoudetecttheproductsurface,nottheinflowingproduct. Fig. 9: mounting of the radar sensor with ...

  • Page 17

    17 4 mounting vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 ca . 10 mm fig. 10: recommended socket mounting ifthereflectivepropertiesofthemediumaregood,youcanmount vegapuls 61 on sockets which are higher than the length of the antenna.Youwillfindrecommendedvaluesforsocketheightsinthe...

  • Page 18

    18 4 mounting vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 socket diameter d socket length h 4" ≤15.8in 6" ≤19.7in acorrespondingcollarflangefordn80(asme3"orjis80)aswell asasuitableadapterflangeareavailableformountingvegapuls 61. With the housing versions plastic, aluminium single c...

  • Page 19

    19 4 mounting vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 socket diameter d socket length h 100 mm ≤400mm 150 mm ≤500mm socket diameter d socket length h 3" ≤11.8in 4" ≤15.8in 6" ≤19.7in in liquids, direct the sensor as perpendicular as possible to the prod- uct surface to achieve ...

  • Page 20

    20 4 mounting vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 fig. 16: agitators throughtheactionoffilling,stirringandotherprocessesinthevessel, compact foam can form on the product surface, damping the emitted signals considerably. If foams are causing measurement errors, the biggest ...

  • Page 21

    21 4 mounting vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 15° 45° 1 2 3 100% 4 5 7 6 0% 8 9 10 fig. 17: configuration surge pipe vegapuls 61 1 radar sensor 2 polarisation marking 3 thread or flange on the instrument 4 vent hole 5 holes 6 welding connection through u-profile 7 ball ...

  • Page 22

    22 4 mounting vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 ø 88,9 mm (3.5") d x 2 26 mm (1.02") 2 mm (0.08") 5 mm (0.20") 80 mm (3.15") 75° 4 mm (0.16") 8 mm (0.32") ø 88,9 mm (3.5") 1 fig. 18: welding connection with surge pipe extension for different example diameters 1 position o...

  • Page 23

    23 4 mounting vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 constructive requirements: • material metal, smooth inner surface • preferably pultruded or straight beaded stainless steel tube • welded joint should be straight and lie in one axis with the holes • flanges are welded to th...

  • Page 24

    24 4 mounting vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 0 % 100 % 1 2 5 4 3 6 fig. 19: configuration bypass 1 radar sensor 2 polarisation marking 3 instrument flange 4 distance sensor reference plane to upper tube connection 5 distance of the tube connections 6 ball valve with co...

  • Page 25

    25 4 mounting vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 constructional requirements on the bypass pipe: • material metal, smooth inner surface • in case of an extremely rough tube inner surface, use an inserted tube (tube in tube) or a radar sensor with tube antenna • flanges are...

  • Page 26

    26 4 mounting vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 2 3 ... 4 x h max 90° h max 1 b fig. 21: flow measurement with khafagi-venturi flume: h max. = max. Filling of the flume; b = tightest constriction in the flume 1 position sensor 2 venturi flume in general, the following poi...

  • Page 27: System

    27 5 connecting to power supply and bus system vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 5 connecting to power supply and bus system 5.1 preparing the connection always keep in mind the following safety instructions: warning: connect only in the complete absence of line voltage. ...

  • Page 28

    28 5 connecting to power supply and bus system vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 box and at the sensor. The screen in the sensor must be connected directly to the internal ground terminal. The ground terminal outside on the housing must be connected to the potential equal...

  • Page 29

    29 5 connecting to power supply and bus system vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 fig. 22: connection steps 5 and 6 5. Insert the wire ends into the terminals according to the wiring plan information: solidcoresaswellasflexiblecoreswithwireendsleevesareinsert- eddirectlyin...

  • Page 30

    30 5 connecting to power supply and bus system vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 5.3 wiring plan 2 1 fig. 23: position of connection compartment (modbus electronics) and electron- ics compartment (sensor electronics) 1 terminal compartment 2 electronics compartment 5 6 7 ...

  • Page 31

    31 5 connecting to power supply and bus system vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 terminal function polarity 1 voltage supply + 2 voltage supply - 3 modbus signal d0 + 4 modbus signal d1 - 5 functional ground with instal- lation according to csa 5.4 double chamber housing ...

  • Page 32

    32 5 connecting to power supply and bus system vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 5.5 switch-on phase after vegapuls 61 is connected to the bus system, the instrument carries out a self-test for approx. 30 seconds. The following steps are carried out: • internal check of t...

  • Page 33: Adjustment Module

    33 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 6 set up the sensor with the display and adjustment module 6.1 adjustment volume the display and adjustment module is only used for parameter adjust- ment of the sensor, i.E. F...

  • Page 34

    34 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 6.3 adjustment system 1 2 fig. 29: display and adjustment elements 1 lc display 2 adjustment keys • [ok] key: – move to the menu overview – confirmselectedmenu – edit parameter...

  • Page 35

    35 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 approx. 60 minutes after the last pressing of a key, an automatic reset tomeasuredvalueindicationistriggered.Anyvaluesnotconfirmed with [ok] will not be saved. 6.4 measured val...

  • Page 36

    36 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 info: instrument name, hardware and software version, date of manu- facture, instrument features information: inthisoperatinginstructionsmanual,theinstrument-specificparam- ete...

  • Page 37

    37 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 through this selection, the sensor is adapted perfectly to the product andmeasurementreliability,particularlyinproductswithpoorreflec- tive properties, is considerably increase...

  • Page 38

    38 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 • installations: small laterally mounted or large top mounted stirrer • process/measurement conditions: – relatively smooth product surface – high requirements on measurement a...

  • Page 39

    39 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 • properties, sensor: – measurementspeedoptimizedbyvirtuallynoaveraging – sporadic false echoes are suppressed – false signal suppression recommended standpipe: • productspeed:...

  • Page 40

    40 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 transportable plastic tank: • vessel: – materialandthicknessdifferent – measurement through the vessel top • process/measurement conditions: – measured value jump with vessel c...

  • Page 41

    41 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 – instrument demonstration – object recognition/monitoring (additional settings required) • properties, sensor: – sensor accepts all measured value changes within the measur- i...

  • Page 42

    42 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 100% 0% 0,5 m (19.68 ") 5 m (196.9 ") 2 1 3 fig. 30: parameter adjustment example min./max. Adjustment 1 min. Level = max. Measuring distance 2 max. Level = min. Measuring dist...

  • Page 43

    43 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 4. Enter the suitable distance value in m for the empty vessel (e.G. Distance from the sensor to the vessel bottom) corresponding to the percentage value. 5. Save settings with...

  • Page 44

    44 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 in the menu item "current output mode" you determine the output characteristics and reaction of the current output in case of failure. The default setting is output characteris...

  • Page 45

    45 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 in the delivery status, the sensor is set to the ordered national lan- guage. Inthismenuitemyoucandefinetheindicationofthemeasuredvalue on the display. The default setting for ...

  • Page 46

    46 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 the respective min. And max. Measured value of the electronics temperature is saved in the sensor. These values as well as the actual temperature value are displayed in the men...

  • Page 47

    47 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 how to interrupt the simulation: → push [esc] information: the simulation is automatically terminated 10 minutes after the last pressing of a key. The "echo curve" shows the si...

  • Page 48

    48 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 thefollowingcircumstancescauseinterferingreflectionsandcan influencethemeasurement: • high sockets • vessel installations such as struts • agitators • buildup or welded joints ...

  • Page 49

    49 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 if a false signal suppression has already been saved in the sensor, the following menu window appears when selecting "false signal suppression": delete: an already created fals...

  • Page 50

    50 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 in delivery status, the pin is "0000". In this menu item, the internal clock of the sensor is adjusted. With a reset, certain parameter adjustments carried out by the user are ...

  • Page 51

    51 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 menu menu item default value setup measurement loop name sensor medium liquid/water bulk solids/crushed stones, gravel application storage tank silo vessel form vessel bottom, ...

  • Page 52

    52 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 themodestandardwiththefixedaddress0meansoutputofthe measured value as 4 … 20 ma signal. In multidrop mode, up to 63 sensors can be operated on one two-wire cable. An address be...

  • Page 53

    53 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 in this menu item, the date of factory calibration of the sensor as well as the date of the last change of sensor parameters are displayed via the display and adjustment module...

  • Page 54: With Pactware

    54 7 setting up sensor and modbus interface with pactware vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 7 setting up sensor and modbus interface with pactware 7.1 connect the pc connection of the pc to the sensor electronics is carried out via the interface adapter vegaconnect. Scope...

  • Page 55

    55 7 setting up sensor and modbus interface with pactware vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 1 fig. 32: connecting the pc via usb to the modbus electronics 1 usb cable to the pc connection of the pc to the rs 485 cable is carried out via a stand- ard interface adapter rs 4...

  • Page 56

    56 7 setting up sensor and modbus interface with pactware vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 tion. The dtms can also be integrated into other frame applications according to fdt standard. Note: to ensure that all instrument functions are supported, you should always use th...

  • Page 57

    57 7 setting up sensor and modbus interface with pactware vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 7.3 set instrument address the vegapuls 61 requires an address for participating as a slave in the modbus communication. The addess setting is carried out via a pc with pactware/dt...

  • Page 58

    58 7 setting up sensor and modbus interface with pactware vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 7.4 saving the parameter adjustment data we recommend documenting or saving the parameter adjustment data via pactware. That way the data are available for multiple use or service ...

  • Page 59

    59 8 diagnosis, asset management and service vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 8 diagnosis, asset management and service 8.1 maintenance if the instrument is used correctly, no maintenance is required in normal operation. 8.2 measured value and event memory the instrument...

  • Page 60

    60 8 diagnosis, asset management and service vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 further echo curves: up to 10 echo curves can be stored in a ring bufferinthismemorysection.Furtherechocurvesarestoredvia: • pc with pactware/dtm • control system with edd 8.3 asset management ...

  • Page 61

    61 8 diagnosis, asset management and service vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 the following table shows the codes and text messages of the status message "failure" and provides information on causes as well as corrective measures. Code text message cause rectification de...

  • Page 62

    62 8 diagnosis, asset management and service vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 code text message cause rectification devspec diagnosis bits f260 error in the calibration – error in the calibration carried out in the factory – error in the eeprom – exchanging the elec- tro...

  • Page 63

    63 8 diagnosis, asset management and service vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 code text message cause rectification devspec state in cmd 48 m500 error with the reset deliv- ery status – with the reset to delivery status, the data could not be restored – repeat reset – lo...

  • Page 64

    64 8 diagnosis, asset management and service vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 • constant level • filling • emptying the images in column "error pattern" show the real level as a broken line and the level displayed by the sensor as a continuous line. 1 2 level time 0 1 re...

  • Page 65

    65 8 diagnosis, asset management and service vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 measurementerrorduringfilling fault description error pattern cause rectification 4. Measured value re- mains unchanged duringfilling level time 0 – false signals in the close range too big or ...

  • Page 66

    66 8 diagnosis, asset management and service vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 measurement error during emptying fault description error pattern cause rectification 11. Measured value re- mains unchanged in the close range during emptying level time 0 – false signal large...

  • Page 67

    67 8 diagnosis, asset management and service vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 in both cases, the serial number of the sensor is needed. The serial numbers are stated on the type label of the instrument, on the inside of the housing as well as on the delivery note. Whenlo...

  • Page 68: 9 Dismount

    68 9 dismount vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 9 dismount 9.1 dismounting steps warning: before dismounting, be aware of dangerous process conditions such as e.G. Pressure in the vessel or pipeline, high temperatures, cor- rosive or toxic products etc. Take note of chapt...

  • Page 69: 10 Supplement

    69 10 supplement vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 10 supplement 10.1 technical data general data 316l corresponds to 1.4404 or 1.4435 materials, wetted parts with encapsulated antenna system Ʋ processfitting pvdf, 316l Ʋ process seal fkm (idg fkm 13-75) Ʋ antenna pvdf ma...

  • Page 70

    70 10 supplement vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 max. Torques, version plastic horn antenna Ʋ mounting screws, mounting strap on sensor housing 4 nm (2.950 lbf ft) Ʋ flangescrews,compressionflange dn 80 5 nm (3.689 lbf ft) Ʋ flangescrews,adapterflangedn100 7 nm (5.163 l...

  • Page 71

    71 10 supplement vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 Ʋ plastic horn antenna up to 20 m (65.62 ft) output variable output Ʋ physical layer digital output signal according to standard eia-485 Ʋ busspecifications modbus application protocol v1.1b3, modbus over se- rial line v1...

  • Page 72

    72 10 supplement vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 0,5 m (1.6 ft) 10 mm (0.394 in) - 10 mm (- 0.394 in) 2 mm (0.079 in) - 2 mm (- 0.079 in) 0 1 2 3 fig. 52: deviation under reference conditions - plastic horn antenna 1 reference plane 2 antenna edge 3 recommended measurin...

  • Page 73

    73 10 supplement vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 ambient conditions ambient, storage and transport tempera- ture -40 … +80 °c (-40 … +176 °f) process conditions fortheprocessconditions,pleasealsonotethespecificationsonthetypelabel.Thelowervalue always applies. Vessel pr...

  • Page 74

    74 10 supplement vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 sensor version configuration,connectioncable cable length standard cable special cable screened 4 … 20 ma/hart 50 m ● – – profibuspa,founda- tion fieldbus 25 m – ● ● integrated clock date format day.Month.Year time format...

  • Page 75

    75 10 supplement vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 protection rating (iec 61010-1) iii approvals instrumentswithapprovalscanhavedifferenttechnicalspecificationsdependingontheversion. For that reason the associated approval documents of these instruments have to be careful...

  • Page 76

    76 10 supplement vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 rtu protocol abbtotalflow modbus rtu, ascii bristol controlwavemicro modbus rtu, ascii fisher roc modbus rtu, ascii scadapack modbus rtu, ascii thermo electron autopilot modbus rtu, ascii parameters for the bus communicat...

  • Page 77

    77 10 supplement vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 register name register number type configurablevalues default value unit parity 202 word 0 = none, 1 = odd, 2 = even 0 - stopbits 203 word 1 = none, 2 = two 1 - delay time 206 word 10 … 250 50 ms byte oder (float- ing poi...

  • Page 78

    78 10 supplement vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 register name register number type note qv 1438 quarternary variable in byte order cdab status 2000 dword see register 100 pv 2002 dword primary variable in byte order abcd (big endian) sv 2004 dword secondary variable in...

  • Page 79

    79 10 supplement vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 10.4 modbus rtu commands fc3 read holding register with this command, any number (1-127) of holding registers can be read out. The start register, from which the readout should start, and the number of registers are trans...

  • Page 80

    80 10 supplement vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 response: parameter length code/data function code 1 byte 0x04 start address 2 bytes 2*n register value 2 bytes data fc8 diagnostics withthisfunctioncodedifferentdiagnosticfunctionscanbetriggeredordiagnosticvaluesreadout....

  • Page 81

    81 10 supplement vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 response: parameter length code/data function code 1 byte 0x10 sub function code 2 bytes 0x0000 to 0xffff data 2 bytes 0x01 to 0x7b fc17 report slave id with this function code, the slave id can be queried. Request: param...

  • Page 82

    82 10 supplement vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 parameter length code/data list of object length 1 byte list of object value 1 byte depending on the object id 10.5 levelmaster commands the vegapuls 61 is also suitable for connection to the following rtus with levelmast...

  • Page 83

    83 10 supplement vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 response: parameter length code/data report level (and temperature) 24 characters ascii uuudlll.Llfttteeeeewwwww uu = address lll.Ll = pv in inches ttt = temperature in fahrenheit eeee = error number (0 no error, 1 level ...

  • Page 84

    84 10 supplement vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 response: parameter length code/data set number of floats 6 characters ascii uuufok if the number is set to 0, no level is returned set baud rate request: parameter length code/data set baud rate 8 (12) characters ascii u...

  • Page 85

    85 10 supplement vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 report receive to transmit delay request: parameter length code/data report receive to transmit delay 4 characters ascii uuur response: parameter length code/data report receive to trans- mit delay 7 characters ascii uuur...

  • Page 86

    86 10 supplement vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 parameter parameter value baud rate 9600 floating point format code 0 rtu data type conversion code 66 input register base number 0 the basic number of the input registers is always added to the input register address of ...

  • Page 87

    87 10 supplement vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 thermo electron autopilot wiring plan + + power suppl y modbus d0 d1 is gnd usb 1 2 3 13 45 2o ff on ( ) ( ) (-) (-) +8 +30 vdc to gnd 2 1 rx - rx+ fig. 56: connection of vegapuls 61 to rtu thermo electron autopilot 1 veg...

  • Page 88

    88 10 supplement vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 bristol controlwave micro wiring plan + + power suppl y modbus d0 d1 is gnd usb 1 2 3 13 45 2o ff on ( ) ( ) (-) (-) +8 +30 vdc to gnd 1 +sv rs 485 on com1 2 rx- 5 rxt 6 txt 3 tx- 4 gnd 7 not used 8 not used fig. 57: conn...

  • Page 89

    89 10 supplement vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 scadapack wiring plan + + power suppl y modbus d0 d1 is gnd usb 1 3 2 13 45 5 2 1 3 4 9 6 7 8 2o ff on ( ) ( ) (-) (-) +8 +30 vdc to gnd com part 3 (c3) rs485 txd- txd+ gnd fig. 58: connection of vegapuls 61 to rtu scadap...

  • Page 90

    90 10 supplement vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 housing 2 1 ø 79 mm (3.11") ~ 84 mm (3.31") m16x1,5 112 mm (4.41") m20x1,5/ ½ npt ~ 87 mm (3.43") m16x1,5 ø 84 mm (3.31") 120 mm (4.72") m20x1,5/ ½ npt fig. 59: dimensions of housing - with integrated display and adjustme...

  • Page 91

    91 10 supplement vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 vegapuls61,hygienicfitting 1 2 3 sw 50 mm (1.97") sw 50 mm (1.97") sw 50 mm (1.97") 121 mm (4.76" ) 121 mm (4.76" ) 121 mm (4.76" ) ø 64 mm (2.52") ø 91 mm (3.58") ø 78 mm (3.07") ø 95 mm (3.74") ø 39 mm (1.54") ø 39 mm (...

  • Page 92

    92 10 supplement vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 vegapuls 61, version with mounting strap 75 mm (2.95") 107 mm (4.21") 115 mm (4.53") 19 mm (0.75") 98 mm (3.86") 15 mm (0.59") 8,5 mm (0.34") 9 mm (0.35") 85 mm (3.35") 12 mm (0.47") 9 mm (0.35") 12 mm (0.47") pp pbt-gf30...

  • Page 93

    93 10 supplement vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 vegapuls 61, version with mounting strap and clamp 9 mm (0.35") 85 mm (3.35") 12 mm (0.47") 125 mm (4.92") 2,5 mm (0.10") 75 mm (2.95") 107 mm (4.21") 115 mm (4.53") 300 mm (11.81") 19 mm (0.75") 117 mm (4.61") 15 mm (0.5...

  • Page 94

    94 10 supplement vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 vegapuls61,versionwithcompressionflange 126 mm (4.96") 10,5 mm (0.41") 19 mm (0.75") ø 75 mm (2.95") ø 115 mm (4.53") ø 156 mm (6.14") ø 200 mm (7.87") ø 21 mm (0.83") ø 107 mm (4.21") fig. 64: vegapuls 61, compression fl...

  • Page 95

    95 10 supplement vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 vegapuls61,versionwithcompressionflangeandrinsingconnection 126 mm (4.96") 10,5 mm (0.41") 15 mm (0.59") 19 mm (0.75") 26,5 mm (1.04") ø 75 mm (2.95") ø 156 mm (6.14") ø 200 mm (7.87") ø 21 mm (0.83") ø 107 mm (4.21") fig...

  • Page 96

    96 10 supplement vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 vegapuls61,versionwithadapterflange 2 1 138 mm (5.43" ) 31 mm (1.22") 20 mm (0.79") 8 mm (0.32") ø 75 mm (2.95") ø 98 mm (3.86") fig. 66: vegapuls 61, adapter flange 1 adapter flange 2 seal.

  • Page 97

    97 10 supplement vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 vegapuls61,versionwithadapterflangeandrinsingconnection 3 2 1 170 mm (6.69") 62,5 mm (2.46") 20 mm (0.79") 34,7 mm (1.37") ø 75 mm (2.95") ø 98 mm (3.86") fig. 67: vegapuls 61, adapter flange 1 rinsing connection 2 reflux...

  • Page 98

    98 10 supplement vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 10.8 industrial property rights vega product lines are global protected by industrial property rights. Further information see www.Vega.Com. Vega produktfamilien sind weltweit geschützt durch gewerbliche schutzrechte. Näh...

  • Page 99: Index

    99 index vegapuls 61 • modbus and levelmaster protocol 41361-en-160224 index a adjustment 42, 43 agitators 19 b backlight 45 c connection procedure 28 connection technology 28 copy sensor settings 52 current output min./max. 44 current output mode 44 d damping 43 date/time 50 default values 50 devia...

  • Page 100

    Printing date: vega grieshaber kg am hohenstein 113 77761 schiltach germany 41361-en-160224 all statements concerning scope of delivery, application, practical use and operat- ing conditions of the sensors and processing systems correspond to the information available at the time of printing. Subjec...