Vega VEGAPULS 61 Operating instructions manual

Manual is about: Radar sensor for continuous level measurement of liquids

Summary of VEGAPULS 61

  • Page 1

    Operating instructions radar sensor for continuous level measurement of liquids vegapuls 61 modbus and levelmaster protocol approval according to lpr radio standard document id: 41717.

  • Page 2: Contents

    2 contents vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 contents 1 about this document 1.1 function ........................................................................................................................... 4 1.2 target group ...........................................

  • Page 3

    3 contents vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 8.2 measured value and event memory ............................................................................... 58 8.3 asset management function .................................................................................

  • Page 4: 1  About This Document

    4 1 about this document vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 1 about this document 1.1 function this operating instructions manual provides all the information you need for mounting, connection and setup as well as important instruc- tionsformaintenanceandfaultrectification....

  • Page 5: 2  For Your Safety

    5 2 for your safety vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 2 for your safety 2.1 authorised personnel all operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator. During work on and wi...

  • Page 6

    6 2 for your safety vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 2.5 ce conformity thedevicefulfillsthelegalrequirementsoftheapplicableecguide- lines.Byaffixingthecemarking,weconfirmsuccessfultestingofthe product. Youcanfindthececertificateofconformityinthedownloadsection of our hom...

  • Page 7

    7 2 for your safety vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 • the mounting location must be at least 4 km away from radio astronomy stations, unless special permission was granted by the responsible national approval authority • when installed within 4 to 40 km of a radio astro...

  • Page 8: 3  Product Description

    8 3 product description vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 3 product description 3.1 configuration thetypelabelcontainsthemostimportantdataforidentificationand use of the instrument: 2 1 15 13 14 12 11 5 3 6 4 7 8 10 9 fig. 1: layout of the type label (example) 1 instrumen...

  • Page 9

    9 3 product description vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 this operating instructions manual applies to the following instrument versions: • sensor electronics: hardware from 1.0.0, software from 4.4.0 • modbus electronics: hardware from 1.0.0, software from 4.4.0 the sco...

  • Page 10

    10 3 product description vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 the delivery must be checked for completeness and possible transit damage immediately at receipt. Ascertained transit damage or con- cealed defects must be appropriately dealt with. Up to the time of installation,...

  • Page 11

    11 3 product description vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 the supplementary electronics is a replacement part for sensors with signal output modbus. Youcanfindfurtherinformationintheoperatinginstructions"supple- mentary electronics modbus" (document-id 41864). The antenn...

  • Page 12: 4 Mounting

    12 4 mounting vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 4 mounting 4.1 general instructions oninstrumentswiththreadedprocessfitting,thehexagonmustbe tightenedwithasuitablewrench.Fortheproperwrenchsizesee chapter "dimensions". Warning: the housing must not be used to screw the ins...

  • Page 13

    13 4 mounting vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 prior to setup you have to replace these protective caps with ap- proved cable glands or close the openings with suitable blind plugs. 4.2 collaroradapterflange formountingtheinstrumentonasocket,acombicompressionflange fordn...

  • Page 14

    14 4 mounting vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 • single chamber housing – angleofinclination180°,infinitelyvariable – angle of inclination in three steps 0°, 90° and 180° • double chamber housing – angleofinclination90°,infinitelyvariable – angle of inclination in two st...

  • Page 15

    15 4 mounting vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 1 2 fig. 5: position of the polarisation 1 marking with version with plastic horn antenna 2 marking with version with encapsulated antenna system when mounting the sensor, keep a distance of at least 200 mm (7.874 in) to the...

  • Page 16

    16 4 mounting vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 fig. 7: mounting of the radar sensor on vessels with conical bottom donotmounttheinstrumentsinorabovethefillingstream.Makesure thatyoudetecttheproductsurface,nottheinflowingproduct. Fig. 8: mounting of the radar sensor with ...

  • Page 17

    17 4 mounting vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 ca . 10 mm fig. 9: recommended socket mounting ifthereflectivepropertiesofthemediumaregood,youcanmount vegapuls 61 on sockets which are higher than the length of the antenna.Youwillfindrecommendedvaluesforsocketheightsinthe ...

  • Page 18

    18 4 mounting vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 socket diameter d socket length h 4" ≤15.8in 6" ≤19.7in acorrespondingcollarflangefordn80(asme3"orjis80)aswell asasuitableadapterflangeareavailableformountingvegapuls 61. With the housing versions plastic, aluminium single c...

  • Page 19

    19 4 mounting vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 socket diameter d socket length h 100 mm ≤400mm 150 mm ≤500mm socket diameter d socket length h 3" ≤11.8in 4" ≤15.8in 6" ≤19.7in in liquids, direct the sensor as perpendicular as possible to the prod- uct surface to achieve ...

  • Page 20

    20 4 mounting vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 fig. 15: agitators throughtheactionoffilling,stirringandotherprocessesinthevessel, compact foam can form on the product surface, damping the emitted signals considerably. If foams are causing measurement errors, the biggest ...

  • Page 21

    21 4 mounting vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 15° 45° 1 2 3 100% 4 5 7 6 0% 8 9 10 fig. 16: configuration surge pipe vegapuls 61 1 radar sensor 2 polarisation marking 3 thread or flange on the instrument 4 vent hole 5 holes 6 welding connection through u-profile 7 ball ...

  • Page 22

    22 4 mounting vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 ø 88,9 mm (3.5") d x 2 26 mm (1.02") 2 mm (0.08") 5 mm (0.20") 80 mm (3.15") 75° 4 mm (0.16") 8 mm (0.32") ø 88,9 mm (3.5") 1 fig. 17: welding connection with surge pipe extension for different example diameters 1 position o...

  • Page 23

    23 4 mounting vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 constructive requirements: • material metal, smooth inner surface • preferably pultruded or straight beaded stainless steel tube • welded joint should be straight and lie in one axis with the holes • flanges are welded to th...

  • Page 24

    24 4 mounting vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 0 % 100 % 1 2 5 4 3 6 fig. 18: configuration bypass 1 radar sensor 2 polarisation marking 3 instrument flange 4 distance sensor reference plane to upper tube connection 5 distance of the tube connections 6 ball valve with co...

  • Page 25

    25 4 mounting vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 constructional requirements on the bypass pipe: • material metal, smooth inner surface • in case of an extremely rough tube inner surface, use an inserted tube (tube in tube) or a radar sensor with tube antenna • flanges are...

  • Page 26

    26 4 mounting vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 2 3 ... 4 x h max 90° h max 1 b fig. 20: flow measurement with khafagi-venturi flume: h max. = max. Filling of the flume; b = tightest constriction in the flume 1 position sensor 2 venturi flume in general, the following poi...

  • Page 27: System

    27 5 connecting to power supply and bus system vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 5 connecting to power supply and bus system 5.1 preparing the connection always keep in mind the following safety instructions: warning: connect only in the complete absence of line voltage. ...

  • Page 28

    28 5 connecting to power supply and bus system vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 box and at the sensor. The screen in the sensor must be connected directly to the internal ground terminal. The ground terminal outside on the housing must be connected to the potential equal...

  • Page 29

    29 5 connecting to power supply and bus system vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 fig. 21: connection steps 5 and 6 - single chamber housing fig. 22: connection steps 5 and 6 - double chamber housing 6. Insert the wire ends into the terminals according to the wiring plan i...

  • Page 30

    30 5 connecting to power supply and bus system vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 9. Tighten the compression nut of the cable entry gland. The seal ring must completely encircle the cable 10. Reinsert the display and adjustment module, if one was installed 11. Screw the ho...

  • Page 31

    31 5 connecting to power supply and bus system vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 + + power supply modbus d0 d1 is gnd usb 1 2 4 3 1 3 4 5 2 off on ( ) ( ) (-) (-) fig. 25: terminal compartment 1 usb interface 2 slide switch for integrated termination resistor (120 Ω) 3 mo...

  • Page 32

    32 5 connecting to power supply and bus system vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 3 4 1 2 fig. 27: view to the plug connector m12 x 1 1 pin 1 2 pin 2 3 pin 3 4 pin 4 contact pin colour connection ca- ble in the sensor terminal, electronics module pin 1 brown 5 pin 2 white ...

  • Page 33: Adjustment Module

    33 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 6 set up the sensor with the display and adjustment module 6.1 adjustment volume the display and adjustment module is only used for parameter adjust- ment of the sensor, i.E. F...

  • Page 34

    34 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 6.3 adjustment system 1 2 fig. 29: display and adjustment elements 1 lc display 2 adjustment keys • [ok] key: – move to the menu overview – confirmselectedmenu – edit parameter...

  • Page 35

    35 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 approx. 60 minutes after the last pressing of a key, an automatic reset tomeasuredvalueindicationistriggered.Anyvaluesnotconfirmed with [ok] will not be saved. 6.4 measured val...

  • Page 36

    36 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 info: instrument name, hardware and software version, date of manu- facture, instrument features information: inthisoperatinginstructionsmanual,theinstrument-specificparam- ete...

  • Page 37

    37 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 through this selection, the sensor is adapted perfectly to the product andmeasurementreliability,particularlyinproductswithpoorreflec- tive properties, is considerably increase...

  • Page 38

    38 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 • installations: small laterally mounted or large top mounted stirrer • process/measurement conditions: – relatively smooth product surface – high requirements on measurement a...

  • Page 39

    39 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 • properties, sensor: – measurementspeedoptimizedbyvirtuallynoaveraging – sporadic false echoes are suppressed – false signal suppression recommended standpipe: • productspeed:...

  • Page 40

    40 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 transportable plastic tank: • vessel: – materialandthicknessdifferent – measurement through the vessel top • process/measurement conditions: – measured value jump with vessel c...

  • Page 41

    41 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 – instrument demonstration – object recognition/monitoring (additional settings required) • properties, sensor: – sensor accepts all measured value changes within the measur- i...

  • Page 42

    42 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 100% 0% 0,5 m (19.68 ") 5 m (196.9 ") 2 1 3 fig. 30: parameter adjustment example min./max. Adjustment 1 min. Level = max. Measuring distance 2 max. Level = min. Measuring dist...

  • Page 43

    43 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 4. Enter the suitable distance value in m for the empty vessel (e.G. Distance from the sensor to the vessel bottom) corresponding to the percentage value. 5. Save settings with...

  • Page 44

    44 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 in the menu item "current output mode" you determine the output characteristics and reaction of the current output in case of failure. The default setting is output characteris...

  • Page 45

    45 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 in the delivery status, the sensor is set to the ordered national lan- guage. Inthismenuitemyoucandefinetheindicationofthemeasuredvalue on the display. The default setting for ...

  • Page 46

    46 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 the respective min. And max. Measured value of the electronics temperature is saved in the sensor. These values as well as the actual temperature value are displayed in the men...

  • Page 47

    47 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 how to interrupt the simulation: → push [esc] information: the simulation is automatically terminated 10 minutes after the last pressing of a key. The "echo curve" shows the si...

  • Page 48

    48 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 thefollowingcircumstancescauseinterferingreflectionsandcan influencethemeasurement: • high sockets • vessel installations such as struts • agitators • buildup or welded joints ...

  • Page 49

    49 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 if a false signal suppression has already been saved in the sensor, the following menu window appears when selecting "false signal suppression": delete: an already created fals...

  • Page 50

    50 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 in delivery status, the pin is "0000". In this menu item, the internal clock of the sensor is adjusted. With a reset, certain parameter adjustments carried out by the user are ...

  • Page 51

    51 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 menu menu item default value setup measurement loop name sensor medium liquid/water bulk solids/crushed stones, gravel application storage tank silo vessel form vessel bottom, ...

  • Page 52

    52 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 themodestandardwiththefixedaddress0meansoutputofthe measured value as 4 … 20 ma signal. In multidrop mode, up to 63 sensors can be operated on one two-wire cable. An address be...

  • Page 53

    53 6 set up the sensor with the display and adjustment module vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 in this menu item, the date of factory calibration of the sensor as well as the date of the last change of sensor parameters are displayed via the display and adjustment module...

  • Page 54: With Pactware

    54 7 setting up sensor and modbus interface with pactware vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 7 setting up sensor and modbus interface with pactware 7.1 connect the pc connection of the pc to the sensor electronics is carried out via the interface adapter vegaconnect. Scope...

  • Page 55

    55 7 setting up sensor and modbus interface with pactware vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 1 fig. 32: connecting the pc via usb to the modbus electronics 1 usb cable to the pc connection of the pc to the rs 485 cable is carried out via a stand- ard interface adapter rs 4...

  • Page 56

    56 7 setting up sensor and modbus interface with pactware vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 tion. The dtms can also be integrated into other frame applications according to fdt standard. Note: to ensure that all instrument functions are supported, you should always use th...

  • Page 57

    57 7 setting up sensor and modbus interface with pactware vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 7.3 saving the parameter adjustment data we recommend documenting or saving the parameter adjustment data via pactware. That way the data are available for multiple use or service ...

  • Page 58

    58 8 diagnosis, asset management and service vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 8 diagnosis, asset management and service 8.1 maintenance if the instrument is used correctly, no maintenance is required in normal operation. 8.2 measured value and event memory the instrument...

  • Page 59

    59 8 diagnosis, asset management and service vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 further echo curves: up to 10 echo curves can be stored in a ring bufferinthismemorysection.Furtherechocurvesarestoredvia: • pc with pactware/dtm • control system with edd 8.3 asset management ...

  • Page 60

    60 8 diagnosis, asset management and service vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 the following table shows the codes and text messages of the status message "failure" and provides information on causes as well as corrective measures. Code text message cause rectification de...

  • Page 61

    61 8 diagnosis, asset management and service vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 code text message cause rectification devspec diagnosis bits f260 error in the calibration – error in the calibration carried out in the factory – error in the eeprom – exchanging the elec- tro...

  • Page 62

    62 8 diagnosis, asset management and service vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 code text message cause rectification devspec state in cmd 48 m500 error with the reset deliv- ery status – with the reset to delivery status, the data could not be restored – repeat reset – lo...

  • Page 63

    63 8 diagnosis, asset management and service vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 • constant level • filling • emptying the images in column "error pattern" show the real level as a broken line and the level displayed by the sensor as a continuous line. 1 2 level time 0 1 re...

  • Page 64

    64 8 diagnosis, asset management and service vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 measurementerrorduringfilling fault description error pattern cause rectification 4. Measured value re- mains unchanged duringfilling level time 0 – false signals in the close range too big or ...

  • Page 65

    65 8 diagnosis, asset management and service vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 measurement error during emptying fault description error pattern cause rectification 11. Measured value re- mains unchanged in the close range during emptying level time 0 – false signal large...

  • Page 66

    66 8 diagnosis, asset management and service vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 in both cases, the serial number of the sensor is needed. The serial numbers are stated on the type label of the instrument, on the inside of the housing as well as on the delivery note. Whenlo...

  • Page 67: 9 Dismount

    67 9 dismount vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 9 dismount 9.1 dismounting steps warning: before dismounting, be aware of dangerous process conditions such as e.G. Pressure in the vessel or pipeline, high temperatures, cor- rosive or toxic products etc. Take note of chapt...

  • Page 68: 10 Supplement

    68 10 supplement vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 10 supplement 10.1 technical data general data 316l corresponds to 1.4404 or 1.4435 materials, wetted parts with encapsulated antenna system Ʋ processfitting pvdf, 316l Ʋ process seal fkm (idg fkm 13-75) Ʋ antenna pvdf ma...

  • Page 69

    69 10 supplement vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 max. Torques, version plastic horn antenna Ʋ mounting screws, mounting strap on sensor housing 4 nm (2.950 lbf ft) Ʋ flangescrews,compressionflange dn 80 5 nm (3.689 lbf ft) Ʋ flangescrews,adapterflangedn100 7 nm (5.163 l...

  • Page 70

    70 10 supplement vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 accuracy (according to din en 60770-1) process reference conditions according to din en 61298-1 Ʋ temperature +18 … +30 °c (+64 … +86 °f) Ʋ relative humidity 45 … 75 % Ʋ air pressure 860 … 1060 mbar/86 … 106 kpa (12.5 … 1...

  • Page 71

    71 10 supplement vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 variablesinfluencingmeasurementaccuracy temperature drift - digital output ±3mm/10k,max.10mm additional deviation through electromag- netic interference acc. To en 61326 characteristics and performance data measuring freq...

  • Page 72

    72 10 supplement vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 wire cross-section (spring-loaded terminals) Ʋ massive wire, stranded wire 0.2 … 2.5 mm² (awg 24 … 14) Ʋ stranded wire with end sleeve 0.2 … 1.5 mm² (awg 24 … 16) display and adjustment module display element display with...

  • Page 73

    73 10 supplement vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 power consumption reverse voltage protection integrated electrical protective measures protection rating housing material version ip-protection class nema protection plastic single chamber ip 66/ip 67 nema4x double chambe...

  • Page 74

    74 10 supplement vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 4 1 3 3 3 2 + + power supply modbus d0 d1 is gnd usb + + power supply modbus d0 d1 is gnd usb + + power supply modbus d0 d1 is gnd usb 1 3 4 5 2 off on ( ) ( ) (-) (-) 1 3 4 5 2 off on ( ) ( ) (-) (-) 1 3 4 5 2 off on ( )...

  • Page 75

    75 10 supplement vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 generalconfigurationofthehost thedataexchangewithstatusandvariablesbetweenfielddeviceandhostiscarriedoutvia register.Forthis,aconfigurationinthehostisrequired.Floatingpointnumberswithshortprevision (4 bytes) according to ...

  • Page 76

    76 10 supplement vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 register name register number type note sv 110 secondary variable in byte order cdab tv unit 112 dword unit code tv 114 third variable in byte order cdab qv unit 116 dword unit code qv 118 quarternary variable in byte ord...

  • Page 77

    77 10 supplement vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 unit codes for register 104, 108, 112, 116 unit code measurement unit 32 degree celsius 33 degree fahrenheit 40 us gallon 41 liters 42 imperial gallons 43 cubic meters 44 feet 45 meters 46 barrels 47 inches 48 centimeters...

  • Page 78

    78 10 supplement vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 request: parameter length code/data function code 1 byte 0x04 start address 2 bytes 0x0000 to 0xffff number of registers n*2 bytes 1 to 127 (0x7d) response: parameter length code/data function code 1 byte 0x04 start addre...

  • Page 79

    79 10 supplement vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 parameter length code/data data n*2 bytes data implemented function codes: sub function code name 0x00 return data request 0x0b return message counter with sub function codes 0x00 only one 16 bit value can be written. Fc1...

  • Page 80

    80 10 supplement vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 fc43sub14,readdeviceidentification withthisfunctioncode,thedeviceidentificationcanbequeried. Request: parameter length code/data function code 1 byte 0x2b mei type 1 byte 0x0e read device id code 1 byte 0x01 to 0x04 objec...

  • Page 81

    81 10 supplement vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 parameter configurablevalues default value address range levelmaster 32 32 the levelmaster commands are based on the following syntax: • capitallettersareatthebeginningofcertaindatafields • smalllettersstandfordatafields ...

  • Page 82

    82 10 supplement vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 response: parameter length code/data report level (and temperature) 6 characters ascii uuunnn assign unit number request: parameter length code/data assign unit number 6 characters ascii uuunnn response: parameter length ...

  • Page 83

    83 10 supplement vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 set receive to transmit delay request: parameter length code/data set receive to transmit delay 7 characters ascii uuurmmm mmm = milliseconds (50 up to 250), default = 127 ms response: parameter length code/data set recei...

  • Page 84

    84 10 supplement vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 10.6 configurationoftypicalmodbushosts fisher roc 809 wiring plan + + power suppl y modbus d0 d1 is gnd usb b com z y a (rx/tx -) (rx/tx +) 1 2 3 13 45 2o ff on ( ) ( ) (-) (-) +8 +30 vdc to gnd fig. 54: connection of veg...

  • Page 85

    85 10 supplement vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 abb total flow wiring plan + + power supply modbus d0 d1 is gnd usb 1 2 13 45 2o ff on ( ) ( ) (-) (-) 8 1 2 6 7 bus + bus - gnd vbat fig. 55: connection of vegapuls 61 to rtu abb total flow 1 vegapuls 61 2 rtu abb total ...

  • Page 86

    86 10 supplement vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 thermo electron autopilot wiring plan + + power suppl y modbus d0 d1 is gnd usb 1 2 3 13 45 2o ff on ( ) ( ) (-) (-) +8 +30 vdc to gnd 2 1 rx - rx+ fig. 56: connection of vegapuls 61 to rtu thermo electron autopilot 1 veg...

  • Page 87

    87 10 supplement vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 bristol controlwave micro wiring plan + + power suppl y modbus d0 d1 is gnd usb 1 2 3 13 45 2o ff on ( ) ( ) (-) (-) +8 +30 vdc to gnd 1 +sv rs 485 on com1 2 rx- 5 rxt 6 txt 3 tx- 4 gnd 7 not used 8 not used fig. 57: conn...

  • Page 88

    88 10 supplement vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 scadapack wiring plan + + power suppl y modbus d0 d1 is gnd usb 1 3 2 13 45 5 2 1 3 4 9 6 7 8 2o ff on ( ) ( ) (-) (-) +8 +30 vdc to gnd com part 3 (c3) rs485 txd- txd+ gnd fig. 58: connection of vegapuls 61 to rtu scadap...

  • Page 89

    89 10 supplement vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 country name of the station geographic latitude geographic longitude france plateau de bure 44°38'01'' n 05°54'26'' e floirac 44°50'10'' n 00°31'37'' w germany effelsberg 50°31'32'' n 06°53'00'' e hungary penc 47°47'22'' ...

  • Page 90

    90 10 supplement vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 housing 2 1 ø 79 mm (3.11") ~ 84 mm (3.31") m16x1,5 112 mm (4.41") m20x1,5/ ½ npt ~ 87 mm (3.43") m16x1,5 ø 84 mm (3.31") 120 mm (4.72") m20x1,5/ ½ npt fig. 59: dimensions of housing - with integrated display and adjustme...

  • Page 91

    91 10 supplement vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 vegapuls 61, version with mounting strap 75 mm (2.95") 107 mm (4.21") 115 mm (4.53") 19 mm (0.75") 98 mm (3.86") 15 mm (0.59") 8,5 mm (0.34") 9 mm (0.35") 85 mm (3.35") 12 mm (0.47") 9 mm (0.35") 12 mm (0.47") pp pbt-gf30...

  • Page 92

    92 10 supplement vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 vegapuls61,versionwithcompressionflange 126 mm (4.96") 10,5 mm (0.41") 19 mm (0.75") ø 75 mm (2.95") ø 115 mm (4.53") ø 156 mm (6.14") ø 200 mm (7.87") ø 21 mm (0.83") ø 107 mm (4.21") fig. 61: vegapuls 61, compression fl...

  • Page 93

    93 10 supplement vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 vegapuls61,versionwithcompressionflangeandairrinsing 126 mm (4.96") 10,5 mm (0.41") 15 mm (0.59") 19 mm (0.75") 26,5 mm (1.04") ø 75 mm (2.95") ø 156 mm (6.14") ø 200 mm (7.87") ø 21 mm (0.83") ø 107 mm (4.21") fig. 62: v...

  • Page 94

    94 10 supplement vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 vegapuls61,versionwithadapterflange 2 1 138 mm (5.43" ) 31 mm (1.22") 20 mm (0.79") 8 mm (0.32") ø 75 mm (2.95") ø 98 mm (3.86") fig. 63: vegapuls 61, adapter flange 1 adapter flange 2 seal.

  • Page 95

    95 10 supplement vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 vegapuls61,versionwithadapterflangeandairrinsing 3 2 1 170 mm (6.69") 62,5 mm (2.46") 20 mm (0.79") 34,7 mm (1.37") ø 75 mm (2.95") ø 98 mm (3.86") fig. 64: vegapuls 61, adapter flange 1 rinsing air connection 2 reflux va...

  • Page 96

    96 10 supplement vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 10.9 industrial property rights vega product lines are global protected by industrial property rights. Further information see www.Vega.Com. Vega produktfamilien sind weltweit geschützt durch gewerbliche schutzrechte. Näh...

  • Page 97: Index

    97 index vegapuls 61 • modbus and levelmaster protocol 41717-en-160224 index a adjustment 42, 43 agitators 19 b backlight 45 c connection 28 copy sensor settings 52 current output min./max. 44 current output mode 44 d damping 43 date/time 50 default values 50 deviation 62 device units 47 e echo curv...

  • Page 98

    98 notes vegapuls 61 • modbus and levelmaster protocol 41717-en-160224.

  • Page 99

    99 notes vegapuls 61 • modbus and levelmaster protocol 41717-en-160224.

  • Page 100

    Printing date: vega grieshaber kg am hohenstein 113 77761 schiltach germany 41717-en-160224 all statements concerning scope of delivery, application, practical use and operat- ing conditions of the sensors and processing systems correspond to the information available at the time of printing. Subjec...