WEG CFW100 User Manual - page 31
30 | CFW100
First Time Power-Up and Start-Up
E
ng
lis
h
5.2.3 Control Type V V W (P202 = 5)
Seq
Display Indication/Action
Seq
Display Indication/Action
1
2
Initialization Mode.
Press key
to enter the first level of the
parameterization mode.
Press keys
or
to select parameter
P202.
3
4
Press key
to change the content of
“P202 – Type of control” for P202 = 5 (V V W ).
Use key
.
Press key
to save the change of P202.
Use key
to select parameter P399.
5
6
If necessary, change the content of
“P399 – Motor rated efficiency” according to
the nameplate.
Press key
for the next parameter.
If necessary, change the content of
“P400 – Motor Rated Voltage”.
Press key
for the next parameter.
7
8
If necessary, change the content of
“P401 - Motor rated current”.
Press key
for the next parameter.
If necessary, change the content of
“P402 – Motor Rated Speed”.
Press key
for the next parameter.
Figure 5.4: Sequence for V V W control