P0268 – DI6 Function
Adjustable
0 to 46 / 0 = Not Used
Factory Setting: P1023 = 0: 0
Range:
0 = Not Used
P1023 = 1: 0
0 = Not Used
P1023 = 2: 0
0 = Not Used
P1023 = 3: 0
0 = Not Used
P1023 = 4: 0
44 = 3rd Speed Reference Digital Input (Application Function 6)
P1023 = 5: 44
0 = Not Used
P1023 = 6: 0
0 = Not Used
P1023 = 7: 0
Proprieties:
Access groups via HMI:
I/O
Description:
This parameter define that the function of the DI6 is to be the 3rd digital input for the selection of the crane
horizontal motion speed reference via the logical combination of digital inputs, as described in the section 3.5.
P0269 – DI7 Function
Adjustable
0 to 45 / 45 = Forward Slowdown Limit Switch (App. Function 7)
Factory Setting: 0
Range:
Proprieties:
CFG
Access groups via HMI:
I/O
Description:
This parameter define that the function of the D7 is “Forward Slowdown Limit Switch” when P1025 = 1.
With logical level “0” (sensor actuated) and with a forward command present, it decelerates the motor down to
the minimum speed defined in P0133.
With logical level “1” (sensor not actuated), it allows commands for load forward or reverse.
P0270 – DI8 Function
Adjustable
0 to 46 / 46 = Reverse Slowdown Limit Switch (App. Function 8)
Factory Setting: 0
Range:
Proprieties:
CFG
Access groups via HMI:
I/O
Description:
This parameter define that the function of the D8 is “Reverse Slowdown Limit Switch” when P1025 = 1.
With logical level “0” (sensor actuated) and with a reverse command present, it decelerates the motor down to
the minimum speed defined in P0133.
With logical level “1” (sensor not actuated), it allows commands for load forward or reverse.
NOTE!
Refer to the CFW500 programming manual for more information on the digital input parameters.
Some parameter options have been removed from the configuration wizard.