Wegner Crane CFW500 series Applications Manual - page 46
Parameters Description
Crane | 46
3.10 ANALOG INPUT
This parameter group allows the user to configure the analog input AI1 for the speed reference control of the
crane motion.
NOTA!
It is configured only when the parameter P1023 (speed reference control configuration) is
programmed with the option 6.
P0231 – AI1 Signal Function
Adjustable
7 = Speed Reference (Application Function 1)
Factory Setting: 7
Range:
Proprieties:
Access groups via HMI:
I/O
Description:
This parameter defines that the function of the analog input AI1 will be the crane speed reference.
P0233 – AI1 Signal Type
Adjustable
0 = 0 to 10 V/20 mA
Factory Setting: 0
Range:
1 = 4 to 20 mA
Proprieties:
Access groups via HMI:
I/O
Description:
This parameter configures the type of signal (voltage or current) that will be read by the analog input AI1.
NOTE!
Refer to the installation guide of the plug-in module used to verify the setting of switch type selection
signal (voltage or current).
P0232 – AI1 Gain
Adjustable
0.000 to 9.999
Factory Setting: 1.000
Range:
Proprieties:
Access groups via HMI:
I/O
Description:
This parameter configure the type of signal (voltage or current) that will be read at each analog input, as well as
its range.
P0234 – AI1 Offset
Adjustable
-100.00 % to +100.00 %
Factory Setting: 0.00 %
Range:
Proprieties:
Access groups via HMI:
I/O
Description:
This parameter add to the measured quantity a value, in percentage, in order to adjust the read variable.