Pacific Energy granville Installation And Operating Instructions Manual - Venting
6
040805-24
GRNA
# 5055.651
Venting
Caution: Only Flex Liner kit (MIND.FL25) or an approved
gas vent flue liner and a Vent Terminal (MIND.VTTERM)
is approved for use with this appliance.
Also approved for use is Simpson Dura-Vent GS
termination kits, both Standard Vertical Termination cap
(#980) and the Extended Vertical Termination cap (#930)
in conjunction with the 3" Co-Linear Termination kit
(#923GK).
No other venting system or components may be used.
1) Measure chimney height and cut flex liner as required.
Mark one of the pipes to identify combustion air intake
pipe from flue outlet pipe.
2) Attach marked flex liner pipe to the intake side (longer
collar) of vent terminal. Seal and secure with sealant and
screws provided. Attach the other pipe to the outlet side of
vent terminal. Seal and secure with sealant and screws
provided.
3) Insert both flex liners from top of the chimney, down
through the damper opening.
4) The vent terminal is sized to fit most typical chimneys.
Before attaching vent terminal to top of chimney, apply a
bead of caulking to top of clay liner. Slip vent terminal
over liner and secure in place with lateral retaining bolts.
5) For larger chimneys, an optional flashing is available
which may be cut and fitted to suit. The flashing attaches
to the underside of the terminal with four nuts provided.
Caulk the flashing in place to seal any gaps.
The vent terminal must be sealed in place to prevent water
from entering the existing chimney.
Fig # 7
Fig # 6
Fig # 8
6) Remove the screw located above the top louver which
retains the vent connector plate on the appliance. Attach
ends of the flex liners to the collars on top of the connector
plate.
Note: The vent must be a minimum 8' long and
must not exceed a total length of 36'.
Min. ........ 8'
(2.4m)
Max. ....... 36' (10.9m)
Vent Terminal
Seal
3" Flex
Liner
Gas Insert