SmartVent Synergy 190 User Manual - page 39
36
HEATER
ON
OFF
Heater
ENABLED
Override
Timer
Normal
?
To deactivate Normal heater mode
either turn the heater OFF on the HEATER
page or change to another heater mode.
?
HEATER
ON
OFF
Heater
ENABLED
Override
Timer
Normal
?
OVERRIDE
1
4
2
6
Override
ON
Hrs
OFF
Use the and arrows to select
the number of hours that you wish the
heater to turn ON for (1, 2, 4 or 6 hours).
The OVERRIDE page will be displayed:
HEATER
ON
OFF
Heater
ENABLED
Override
Timer
Normal
?
To enable the Override mode press the
Override tab:
Note: Normal mode is the default mode. Synergy
will automatically select this mode when the
heater is turned ON, providing neither of the
other two modes were active prior to the heater
being turned OFF.
If a different mode is active and you
wish to enable Normal mode, press the
Normal tab:
OVERRIDE HEATER MODE
Override mode allows you to turn the
heater ON, irrespective of any other
variable settings. This mode is useful to
temper the incoming air in situations
where the internal heating has been off
and human activity is at a minimum.
NORMAL HEATER MODE
Normal mode is driven by the Minimum
Temperature setting. If the heater is
enabled and this mode is active, it will
automatically turn the tempering heater
ON when your Control Room drops
below the minimum temperature and
OFF again when it rises 1°C above your
minimum temperature setting.
The Normal tab border is highlighted
blue indicating this mode is active: