End of Programming
This menu allows to finish the programming (both default
and personalized) saving the modified data into memory.
no
Further corrections to carry out: do not quit the
programming.
Si
changes complete: when programming is
complete and the data is saved, the display
shows the control panel
THE INSERTED DATA HAVE BEEN MEMORIZED: THE
CONTROL UNIT IS READY TO BE USED.
18.1 - OPERATION DEFECTS
This paragraph shows some possible operation defects, along
with their cause and applicable remedy.
Error 1
The following writing appears on display when you exit from
programming
Err 1
It means that changed data could not be stored.
This kind of defect has no remedy and the control unit must be
sent to V2 SPA for repair.
Error 2
When a Start command is given and the gate does not open and
the following writing appears on display
Err2
It means that MOSFET test failed.
Before sending the control unit to V2 SPA for repair, be sure
that motors have been properly connected.
Error 3
When a Start command is given and the door does not open and
the following writing appears on display
Err3
It means that the photocell test failed.
1.
Be sure that no obstacle interrupted the photocell beam
when the Start command was given.
2.
Be sure that photocells, as enabled by their relevant menus,
have been installed actually.
3.
If you have photocells 2, be sure that
Fot2
menu item is on
CF.CH
.
4.
Be sure that photocells are powered and working; when you
interrupt their beam, you should hear the relay tripping.
Error 4
When a Start command is given and the gate does not open
(or does a partial opening) and the following writing appears on
display
Err4
It means that the end of stroke is damaged or that the wiring
that connects the sensor to the control unit is broken.
Change the end of stroke sensor or the broken wiring.
If the error persists send the control unit to V2 for repair.
If the error persists send the control unit to V2 S.p.A. for repair.
Error 5
Once given a start control, the gate does not open and the
display shows
Err5
It means that the test of the safety edges failed.
Check that the menu of the test of safety edges (
Co.tE
) have
been set correctly.
Check that the safety edges enabled from the menu are
installed.
Error 9
When you are trying to change the control unit setups and the
following writing appears on display
Err9
It means that programming was locked by means of the
programming lock key CL1+ (code 161213).
To change the settings it is necessary to insert in the connector
of the ADI interface the same key used to activate the
programming lock, and unlock the device
OVERLOAD led is on
It means that there is an overload on accessory power supply.
1.
Remove the extractable part containing terminals
J1
to
J9
.
OVERLOAD led will switch off.
2.
Remove the overload cause.
3.
Reinsert the terminal board extractable part and check that
this led is not on again.
Control unit setting
This menu allows to set the motor as MASTER or SLAVE.
Mt
MASTER motor
SL
SLAVE motor
If the installation only includes a single motor select the
MT
parameter
(default). If the installation includes two motors carefully read the
chapter 16, then proceed with the CFG parameter setting
NOTE:
If you set
SL
, all the other menu items are no longer accessible.
Only the Fine menu will be available