Vega VEGAPULS 69 Operating Instructions Manual
Summary of VEGAPULS 69
Page 1
Operating instructions radar sensor for continuous level measurement of bulk solids vegapuls 69 foundation fieldbus document id: 47251.
Page 2: Contents
2 contents vegapuls 69 • foundation fieldbus 47251-en-160815 contents 1 about this document 1.1 function ........................................................................................................................... 4 1.2 target group .......................................................
Page 3
3 contents vegapuls 69 • foundation fieldbus 47251-en-160815 8.2 field communicator 375, 475 ........................................................................................ 55 9 diagnosis, asset management and service 9.1 maintenance ............................................................
Page 4: 1 About This Document
4 1 about this document vegapuls 69 • foundation fieldbus 47251-en-160815 1 about this document 1.1 function this operating instructions manual provides all the information you need for mounting, connection and setup as well as important instruc- tionsformaintenanceandfaultrectification.Pleasereadth...
Page 5: 2 For Your Safety
5 2 for your safety vegapuls 69 • foundation fieldbus 47251-en-160815 2 for your safety 2.1 authorised personnel all operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator. During work on and with the devic...
Page 6
6 2 for your safety vegapuls 69 • foundation fieldbus 47251-en-160815 2.5 ce conformity thedevicefulfilsthelegalrequirementsoftheapplicableeuguide- lines.Byaffixingthecemarking,weconfirmtheconformityofthe instrument with these guidelines. Youcanfindtheeuconformitydeclarationonourwebsiteunder www.Veg...
Page 7
7 2 for your safety vegapuls 69 • foundation fieldbus 47251-en-160815 • the instrument must be stationary mounted and the antenna directed vertically downward • the mounting location must be at least 4 km away from radio astronomy stations, unless special permission was granted by the responsible na...
Page 8
8 2 for your safety vegapuls 69 • foundation fieldbus 47251-en-160815 • the use of this device is on a “no-interference, no-protection” basis. That is, the user shall accept operations of high-powered radar in the same frequency band which may interfere with or damage this device. However, level pro...
Page 9: 3 Product Description
9 3 product description vegapuls 69 • foundation fieldbus 47251-en-160815 3 product description 3.1 configuration thetypelabelcontainsthemostimportantdataforidentificationand use of the instrument: 2 1 14 15 13 12 11 5 6 4 3 7 8 9 10 fig. 1: layout of the type label (example) 1 instrument type 2 pro...
Page 10
10 3 product description vegapuls 69 • foundation fieldbus 47251-en-160815 • scan the data matrix code on the type label of the instrument or • enter the serial number manually in the app this operating instructions manual applies to the following instrument versions: • hardware version from 1.0.0 •...
Page 11
11 3 product description vegapuls 69 • foundation fieldbus 47251-en-160815 viaspecialalgorithmsinthesensorelectronics.Thedeterminedfill- ing height is then converted into a corresponding output signal and outputted as the measured value. 3.3 packaging, transport and storage your instrument was prote...
Page 12
12 3 product description vegapuls 69 • foundation fieldbus 47251-en-160815 the vegadis 81 is an external display and adjustment unit for vega plics ® sensors. For sensors with double chamber housing the interface adapter "disadapt" is also required for vegadis 81. Youcanfindfurtherinformationintheop...
Page 13
13 3 product description vegapuls 69 • foundation fieldbus 47251-en-160815 electronics module "vegapuls series 60" is a replacement part for radarsensorsofvegapulsseries60.Adifferentversionisavailable for each type of signal output. Youcanfindfurtherinformationintheoperatinginstructions"elec- tronic...
Page 14: 4 Mounting
14 4 mounting vegapuls 69 • foundation fieldbus 47251-en-160815 4 mounting 4.1 general instructions protect your instrument against moisture ingress through the following measures: • use the recommended cable (see chapter "connectingtopower supply") • tighten the cable gland • loop the connection ca...
Page 15
15 4 mounting vegapuls 69 • foundation fieldbus 47251-en-160815 4.2 mounting versions, plastic horn antenna the optional mounting strap allows simple mounting of the instrument on a wall, ceiling or boom. Especially in the case of open vessels, this isasimpleandeffectivewaytoalignthesensortothesurfa...
Page 16
16 4 mounting vegapuls 69 • foundation fieldbus 47251-en-160815 fig. 4: wall mounting with inclined wall via the mounting strap with length 300 mm two versions are available for mounting the instrument on a socket: • suitable for • combicompressionflange thecombicompressionflangeissuitablefordiffere...
Page 17
17 4 mounting vegapuls 69 • foundation fieldbus 47251-en-160815 3 1 2 fig.6:adapterflange 1 connectionscrew 2 adapterflange 3 process seal 4.3 mounting preparations, mounting strap the mounting strap is supplied unassembled (optionally) and must be screwed to the sensor before setup with three hexag...
Page 18
18 4 mounting vegapuls 69 • foundation fieldbus 47251-en-160815 4.4 mounting instructions radar sensors for level measurement emit electromagnetic waves. Thepolarizationisthedirectionoftheelectricalcomponentofthese waves. Thepolarizationdirectionismarkedbyanoseonthehousing,see following drawing: 1 f...
Page 19
19 4 mounting vegapuls 69 • foundation fieldbus 47251-en-160815 fig.10:mountingoftheradarsensorwithinflowingmedium silowithlateralfilling inbulksolidssiloswithlateralpneumaticfillingtheinstrumentshould notbemountedabovethefillingstream,astheradarsignalwillbe disrupted.Theoptimalmountingpositionistot...
Page 20
20 4 mounting vegapuls 69 • foundation fieldbus 47251-en-160815 fig.11:mountingoftheradarsensorwithinflowingmedium information: the mounting socket should be as short as possible and its end rounded. This reduces false echoes from the vessel mounting socket. Fig. 12: recommended socket mounting ifth...
Page 21
21 4 mounting vegapuls 69 • foundation fieldbus 47251-en-160815 d h the below charts specify the max. Pipe socket length h depending on the diameter d. Socket diameter d socket length h 80 mm ≤200mm 100 mm ≤300mm 150 mm ≤500mm socket diameter d socket length h 3" ≤7.87in 4" ≤11.8in 6" ≤19.7in in ord...
Page 22
22 4 mounting vegapuls 69 • foundation fieldbus 47251-en-160815 r r r... / 1 3 / 1 2 fig. 14: mounting position and orientation with the help of an optional swivelling holder, the sensor can be easily aligned to the vessel centre. The necessary angle of inclination depends on the vessel dimensions. ...
Page 23
23 4 mounting vegapuls 69 • foundation fieldbus 47251-en-160815 d a α fig.15:proposalforinstallationafterorientationvegapuls69 the following table shows the necessary angle of inclination. It depends on the measuring distance and the distance "a" between vessel centre and installation position. Dist...
Page 24
24 4 mounting vegapuls 69 • foundation fieldbus 47251-en-160815 distance d (m) 2° 4° 6° 8° 10° 80 2.8 5.6 8.4 11.1 13.9 90 3.1 6.3 9.4 12.5 15.6 100 3.5 7 10.5 13.9 17.4 110 3.8 7.7 11.5 15.3 19.1 120 4.2 8.4 12.5 16.7 20.8 example: in a vessel 20 m high, the installation position of the sensor is 1...
Page 25
25 4 mounting vegapuls 69 • foundation fieldbus 47251-en-160815 fig.17:coverflat,large-areaprofileswithdeflectors large material heaps are best measured with several instruments, which can be mounted on e.G. Traverse cranes. For this type of ap- plication it is advantageous to orient the sensor perp...
Page 26
26 4 mounting vegapuls 69 • foundation fieldbus 47251-en-160815 max. 50 mm (1.97" ) 1 2 3 fig. 19: mounting the instrument on insulated vessels. 1 electronicshousing 2 spacer 3 vessel insulation thewallsofmultiple-chambersilosareoftenmadeofprofilematerial, e.G.Profilesheeting,toensuretherequiredstab...
Page 27
27 4 mounting vegapuls 69 • foundation fieldbus 47251-en-160815 fig. 21: installation and orientation in multiple chamber silos to avoid heavy buildup and dust on the antenna, the sensor should not be mounted close to the dust exhauster inside the vessel. To protect the sensor against buildup, parti...
Page 28
28 4 mounting vegapuls 69 • foundation fieldbus 47251-en-160815 fig.23:rinsingairconnectionwithcompressionflange fig.24:rinsingairconnectionwithadapterflange youcanfinddetailsontherinsingairconnectioninchapter"technical data"..
Page 29
29 5 connecting to the bus system vegapuls 69 • foundation fieldbus 47251-en-160815 5 connecting to the bus system 5.1 preparing the connection always keep in mind the following safety instructions: warning: connect only in the complete absence of line voltage. • the electrical connection must only ...
Page 30
30 5 connecting to the bus system vegapuls 69 • foundation fieldbus 47251-en-160815 directly to the internal ground terminal. The ground terminal outside on the housing must be connected to the potential equalisation (low impedance). 5.2 connecting the voltage supply and signal output are connected ...
Page 31
31 5 connecting to the bus system vegapuls 69 • foundation fieldbus 47251-en-160815 fig.26:connectionsteps5and6-doublechamberhousing 6. Insert the wire ends into the terminals according to the wiring plan information: solidcoresaswellasflexiblecoreswithwireendsleevesareinsert- eddirectlyintothetermi...
Page 32
32 5 connecting to the bus system vegapuls 69 • foundation fieldbus 47251-en-160815 5.3 wiring plan, single chamber housing 1 2 ( ) (-) 1 5 0 1 0 1 + 6 7 8 bus 2 3 4 5 fig.27:electronicsandterminalcompartment,singlechamberhousing 1 voltage supply, signal output 2 contactpinsforthedisplayandadjustmen...
Page 33
33 5 connecting to the bus system vegapuls 69 • foundation fieldbus 47251-en-160815 bus 5 1 2 + ( ) (-) 6 7 8 2 3 4 1 fig.29:terminalcompartment,doublechamberhousing 1 voltage supply, signal output 2 for display and adjustment module or interface adapter 3 for external display and adjustment unit 4 ...
Page 34
34 5 connecting to the bus system vegapuls 69 • foundation fieldbus 47251-en-160815 5.5 double chamber housing with disadapt 3 1 2 fig.31:viewtotheelectronicscompartmentwithdisadaptforconnectionof the external display and adjustment unit 1 disadapt 2 internal plug connection 3 plug connector m12 x 1...
Page 35
35 5 connecting to the bus system vegapuls 69 • foundation fieldbus 47251-en-160815 then the actual measured value is outputted to the signal cable. The value takes into account settings that have already been carried out, e.G. Default setting..
Page 36: Module
36 6 set up with the display and adjustment module vegapuls 69 • foundation fieldbus 47251-en-160815 6 set up with the display and adjustment module 6.1 insert display and adjustment module the display and adjustment module can be inserted into the sensor andremovedagainatanytime.Youcanchooseanyoneo...
Page 37
37 6 set up with the display and adjustment module vegapuls 69 • foundation fieldbus 47251-en-160815 1 2 fig. 34: installing the display and adjustment module in the double chamber housing 1 in the electronics compartment 2 in the terminal compartment note: ifyouintendtoretrofittheinstrumentwithadis...
Page 38
38 6 set up with the display and adjustment module vegapuls 69 • foundation fieldbus 47251-en-160815 – move to the menu overview – confirmselectedmenu – edit parameter – save value • [->] key: – change measured value presentation – select list entry – select menu items in the quick setup menu – sele...
Page 39
39 6 set up with the display and adjustment module vegapuls 69 • foundation fieldbus 47251-en-160815 this menu item is used to select the national language for further pa- rameter adjustment. You can change the selection via the menu item "setup - display, menu language". With the "ok" key you move ...
Page 40
40 6 set up with the display and adjustment module vegapuls 69 • foundation fieldbus 47251-en-160815 info: instrument name, hardware and software version, date of manu- facture, device id, instrument features in the main menu item "setup", the individual submenu items should be selected one after th...
Page 41
41 6 set up with the display and adjustment module vegapuls 69 • foundation fieldbus 47251-en-160815 information: the min. Adjustment must be carried out independently of this. The following features form the basis of the applications: silo (slender and high): • vessel of metal: weld joints • proces...
Page 42
42 6 set up with the display and adjustment module vegapuls 69 • foundation fieldbus 47251-en-160815 – measuredvaluejumps,e.G.Bytheprofileoftheheaportrav- erses – large angles of repose – measurementnearthefillingstream • properties, sensor: – mean averaging – high measured value jumps are accepted ...
Page 43
43 6 set up with the display and adjustment module vegapuls 69 • foundation fieldbus 47251-en-160815 2 1 3 100% 0% 1 m (39.37 ") 35 m (1378 ") fig.36:parameteradjustmentexamplemin./max.Adjustment 1 min. Level = max. Measuring distance 2 max. Level = min. Measuring distance 3 reference plane if these...
Page 44
44 6 set up with the display and adjustment module vegapuls 69 • foundation fieldbus 47251-en-160815 4. For the full vessel, enter the distance value in m matching the percentage value. 5. Save settings with [ok] and move with [esc] and [->] to min. Adjustment. Proceed as follows: 1. Select with [->...
Page 45
45 6 set up with the display and adjustment module vegapuls 69 • foundation fieldbus 47251-en-160815 • select menu items and show data • read data from the sensor into the display and adjustment mod- ule. Releasing the sensor adjustment is also possible in any menu item by entering the pin. Caution:...
Page 46
46 6 set up with the display and adjustment module vegapuls 69 • foundation fieldbus 47251-en-160815 the display and adjustment module has a backlight for the display. In thismenuitemyoucanswitchthelightingonoroff.Youcanfindthe required operating voltage in chapter "technicaldata". In delivery statu...
Page 47
47 6 set up with the display and adjustment module vegapuls 69 • foundation fieldbus 47251-en-160815 in this menu item you can simulate measured values via the current output. This allows the signal path to be tested, e.G. Through down- stream indicating instruments or the input card of the control ...
Page 48
48 6 set up with the display and adjustment module vegapuls 69 • foundation fieldbus 47251-en-160815 in this menu item, the internal clock of the sensor is set to the request- ed time and time format. At the time of shipment from factory, the instrument is set to cet (central european time). During ...
Page 49
49 6 set up with the display and adjustment module vegapuls 69 • foundation fieldbus 47251-en-160815 menu menu item default value setup units distance in m temperature in °c application medium: crushed stones/gravel application: silo vessel bottom: flat vessel height/measuring range: 120 m min. Adju...
Page 50
50 6 set up with the display and adjustment module vegapuls 69 • foundation fieldbus 47251-en-160815 • high sockets • vessel internals such as struts • agitators • buildup or welded joints on vessel walls note: a false signal suppression detects, marks and saves these false signals so that they are ...
Page 51
51 6 set up with the display and adjustment module vegapuls 69 • foundation fieldbus 47251-en-160815 delete: an already created false signal suppression will be com- pletely deleted. This is useful if the saved false signal suppression no longer matches the metrological conditions in the vessel. Ext...
Page 52
52 6 set up with the display and adjustment module vegapuls 69 • foundation fieldbus 47251-en-160815 in this menu item, the ff device id of the instrument will be dis- played: in this menu item, the features of the sensor such as approval, pro- cessfitting,seal,measuringrange,electronics,housingando...
Page 53: 7 Setup With Pactware
53 7 setup with pactware vegapuls 69 • foundation fieldbus 47251-en-160815 7 setup with pactware 7.1 connect the pc 3 1 2 fig.37:connectionofthepcdirectlytothesensorviatheinterfaceadapter 1 usbcabletothepc 2 interfaceadaptervegaconnect 3 sensor 7.2 parameter adjustment for parameter adjustment of th...
Page 54
54 7 setup with pactware vegapuls 69 • foundation fieldbus 47251-en-160815 fig.38:exampleofadtmview all device dtms are available as a free-of-charge standard version and as a full version that must be purchased. In the standard version, all functions for complete setup are already included. An assi...
Page 55
55 8 set up with other systems vegapuls 69 • foundation fieldbus 47251-en-160815 8 set up with other systems 8.1 dd adjustment programs device descriptions as enhanced device description (edd) are available for dd adjustment programs such as, for example, ams™ and pdm. Thefilescanbedownloadedatwww.V...
Page 56
56 9 diagnosis, asset management and service vegapuls 69 • foundation fieldbus 47251-en-160815 9 diagnosis, asset management and service 9.1 maintenance if the instrument is used correctly, no maintenance is required in normal operation. Insomeapplications,buildupontheantennasystemcaninfluence the m...
Page 57
57 9 diagnosis, asset management and service vegapuls 69 • foundation fieldbus 47251-en-160815 • pc with pactware/dtm • control system with edd • display and adjustment module further echo curves: up to 10 echo curves can be stored in a ring bufferinthismemorysection.Furtherechocurvesarestoredvia: •...
Page 58
58 9 diagnosis, asset management and service vegapuls 69 • foundation fieldbus 47251-en-160815 still valid. Plan in maintenance for the instrument because a failure is expected in the near future (e.G. Due to buildup). This status message is inactive by default. It can be activated by the user via p...
Page 59
59 9 diagnosis, asset management and service vegapuls 69 • foundation fieldbus 47251-en-160815 code text message cause rectification devspec diagnosis bits f125 impermissible electronics temperature – temperature of the electronics in the non- specifiedrange – check ambient tem- perature – isolate e...
Page 60
60 9 diagnosis, asset management and service vegapuls 69 • foundation fieldbus 47251-en-160815 code text message cause rectification devspec state diagno- sis bits s601 overfilling – danger of vessel overfilling – make sure that there is nofurtherfilling – check level in the vessel bit 24 s603 imper...
Page 61
61 9 diagnosis, asset management and service vegapuls 69 • foundation fieldbus 47251-en-160815 code text message cause rectification devspec diagnosis bits m507 error in the instrument set- tings – error during setup – error when carrying out a reset – false signal suppression faulty – carry out res...
Page 62
62 9 diagnosis, asset management and service vegapuls 69 • foundation fieldbus 47251-en-160815 measurement error with constant level fault description error pattern cause rectification 1. Measured value shows a too low or too high level level time 0 – min./max. Adjustment not correct – adapt min./ma...
Page 63
63 9 diagnosis, asset management and service vegapuls 69 • foundation fieldbus 47251-en-160815 measurement error during emptying fault description error pattern cause rectification 6. Measured value re- mains unchanged in the close range during emptying level time 0 – false signal larger than the le...
Page 64
64 9 diagnosis, asset management and service vegapuls 69 • foundation fieldbus 47251-en-160815 the new electronics module must be loaded with the default settings of the sensor. These are the options: • in the factory • or on site by the user in both cases, the serial number of the sensor is needed....
Page 65
65 9 diagnosis, asset management and service vegapuls 69 • foundation fieldbus 47251-en-160815 • please contact the agency serving you to get the address for thereturnshipment.Youcanfindtheagencyonourhomepage www.Vega.Com..
Page 66: 10 Dismount
66 10 dismount vegapuls 69 • foundation fieldbus 47251-en-160815 10 dismount 10.1 dismounting steps warning: before dismounting, be aware of dangerous process conditions such as e.G. Pressure in the vessel or pipeline, high temperatures, cor- rosive or toxic products etc. Take note of chapters "moun...
Page 67: 11 Supplement
67 11 supplement vegapuls 69 • foundation fieldbus 47251-en-160815 11 supplement 11.1 technical data note for approved instruments the technical data in the respective safety instructions are valid for approved instruments (e.G. With exapproval).Thesedatacandifferfromthedatalistedherein,forexamplere...
Page 68
68 11 supplement vegapuls 69 • foundation fieldbus 47251-en-160815 Ʋ fixing screws, mounting strap 316l Ʋ fixingscrews,adapterflange 304 Ʋ plastic housing plastic pbt (polyester) Ʋ aluminium die-casting housing aluminium die-casting alsi10mg, powder-coated - basis: polyester Ʋ stainless steel housin...
Page 69
69 11 supplement vegapuls 69 • foundation fieldbus 47251-en-160815 channel numbers Ʋ channel 1 process value Ʋ channel 8 electronics temperature transmission rate 31.25 kbit/s current value Ʋ non-ex and ex ia instrument 12 ma, ±0.5 ma Ʋ ex-d-ia instruments 16 ma, ±0.5 ma resolution, digital > 1 mm (...
Page 70
70 11 supplement vegapuls 69 • foundation fieldbus 47251-en-160815 variablesinfluencingmeasurementaccuracy temperature drift - digital output ±3 mm/10 k, max. 10 mm characteristics and performance data measuring frequency w-band(79ghztechnology) measuring cycle time approx. 700 ms step response time...
Page 71
71 11 supplement vegapuls 69 • foundation fieldbus 47251-en-160815 1 2 0 °c (32 °f) -40 °c (-104 °f) 80 °c (176 °f) 80 °c (176 °f) -40 °c (-104 °f) fig. 51: ambient temperature - process temperature, plastic horn antenna 1 ambient temperature 2 process temperature 1 2 3 4 a b 0°c / 32°f -40°c / -40°...
Page 72
72 11 supplement vegapuls 69 • foundation fieldbus 47251-en-160815 0°c / 32°f -40°c / -40°f 80°c / 176°f 54°c / 129°f 49°c / 120°f 63°c / 145°f 200°c 392°f 150°c 302°f 100°c 212°f 50°c 122°f 80°c 176°f -40°c -40°f 1 / 2 3 4 a b fig.53:ambienttemperature-processtemperature,metal-jacketedlensantennaup...
Page 73
73 11 supplement vegapuls 69 • foundation fieldbus 47251-en-160815 max. Permissible pressure 6 bar (87.02 psig) air quality filtered air volume, depending on pressure metal-jacketed lens antenna air volume pressure withoutrefluxvalve withrefluxvalve 0.2 bar (2.9 psig) 1.7 m 3 /h - 0.4 bar (5.8 psig)...
Page 74
74 11 supplement vegapuls 69 • foundation fieldbus 47251-en-160815 electromechanical data - version ip 66/ip 67 and ip 66/ip 68; 0.2 bar options of the cable entry Ʋ cable entry m20 x 1.5, ½ npt Ʋ cable gland m20 x 1,5; ½ npt (cable ø see below table) Ʋ blind plug m20 x 1.5; ½ npt Ʋ closing cap ½ np...
Page 75
75 11 supplement vegapuls 69 • foundation fieldbus 47251-en-160815 protection rating Ʋ unassembled ip 20 Ʋ mounted in the housing without lid ip 40 ambient temperature - display and adjustment module -20 … +70 °c (-4 … +158 °f) materials Ʋ housing abs Ʋ inspection window polyester foil interface to ...
Page 76
76 11 supplement vegapuls 69 • foundation fieldbus 47251-en-160815 Ʋ ex-ia instrument - power supply fisco model 13.5 … 17.5 v dc Ʋ ex-ia instrument - power supply entity model 13.5 … 24 v dc Ʋ ex-d-ia instrument no lighting possible (integrated ia barrier) power supply by/max. Number of sensors Ʋ f...
Page 77
77 11 supplement vegapuls 69 • foundation fieldbus 47251-en-160815 country name of the station geographic latitude geographic longitude pico veleta 37°03'58" n 03°23'34" w sweden onsala 57°23’45" n 11°55’35" e 11.3 supplementary information foundation fieldbus the following table gives you an overvi...
Page 78
78 11 supplement vegapuls 69 • foundation fieldbus 47251-en-160815 general information las (link active scheduler) yes master capable yes number of vcrs (virtual communication re- lationships) 24 function blocks transducer block (tb) the transducer block "analog input (ai)" takes the original measur...
Page 79
79 11 supplement vegapuls 69 • foundation fieldbus 47251-en-160815 fig. 56: schematic presentation function block discret input (di) function block pid control the function block "pidcontrol" is a key component for various tasks in the process automation andisuseduniversally.Pidblockscanbecascadedif...
Page 80
80 11 supplement vegapuls 69 • foundation fieldbus 47251-en-160815 function block signal characterizer the function block "signalcharacterizer" has two channels the outputs of which are not in linear relationwiththerespectiveinput.Thenon-linearrelationisdefinedbyalook-uptablewithindividu- ally selec...
Page 81
81 11 supplement vegapuls 69 • foundation fieldbus 47251-en-160815 an output signal according to the selection criteria. Typical input signals are ai blocks. Selection possibilitiesaremaximum,minimum,meanvalue,averagevalueandfirstusefulsignal.Through parameter combination, the block can be used as r...
Page 82
82 11 supplement vegapuls 69 • foundation fieldbus 47251-en-160815 parameter list the following table gives you an overview of the parameters used. Ff desciptor description unit primary_value primary_value(linearizedvalue).Thisistheprocessval- ueaftermin/maxadjustmentandlinearizationwiththestatus of...
Page 83
83 11 supplement vegapuls 69 • foundation fieldbus 47251-en-160815 ff desciptor description unit application_config medium type, media, application type, vessel bottom, vessel height linearization_type_sel typeoflinearization simulation_physcal integration_data physicaloffsetandintegrationtime devic...
Page 84
84 11 supplement vegapuls 69 • foundation fieldbus 47251-en-160815 ff desciptor description unit lin_table_a … lin_ table_q 32 couples of percentage and lin. Percentage values electronics_informa- tion electronics version application_config_ service limitation measuring range begin, safety of measur...
Page 85
85 11 supplement vegapuls 69 • foundation fieldbus 47251-en-160815 plastic housing ~ 69 mm (2.72") ø 79 mm (3.11") 112 mm (4.41") m20x1,5/ ½ npt ~ 84 mm (3.31") m16x1,5 112 mm (4.41") m20x1,5/ ½ npt 1 2 ø 79 mm (3.11") fig.63:housingversionswithprotectionratingip66/ip67-withintegrateddisplayandadjus...
Page 86
86 11 supplement vegapuls 69 • foundation fieldbus 47251-en-160815 aluminium housing with protection rating ip 66/ip 68 (1 bar) 120 mm (4.72") ~ 105 mm (4.13") 116 mm (4.57") ~ 150 mm (5.91") ø 86 mm (3.39") ø 86 mm (3.39") m20x1,5/ ½ npt m16x1,5 2 m20x1,5 m20x1,5 1 fig.65:housingversionwithprotecti...
Page 87
87 11 supplement vegapuls 69 • foundation fieldbus 47251-en-160815 stainless steel housing with protection rating ip 66/ip 68, 1 bar 117 mm (4.61") ~ 103 mm (4.06") ø 79 mm (3.11") 120 mm (4.72") ~ 105 mm (4.13") ø 86 mm (3.39") m20x1,5 m20x1,5/ ½ npt m16x1,5 ~ 93 mm (3.66") ø 80 mm (3.15") 112 mm (...
Page 88
88 11 supplement vegapuls 69 • foundation fieldbus 47251-en-160815 vegapuls69,plastichornantennawithcompressionflangeandrinsingconnection 126 mm (4.96") 14,7 mm (0.58") 10,5 mm (0.41") 26,5 mm (1.04") 19 mm (0.75") ø 75 mm (2.95") ø 156 mm (6.14") ø 200 mm (7.87") ø 21 mm (0.83") ø 107 mm (4.21") 1 ...
Page 89
89 11 supplement vegapuls 69 • foundation fieldbus 47251-en-160815 vegapuls69,plastichornantennawithadapterflange 2 1 144 mm (5.67") 36,5 mm (1.44") 20 mm (0.79") 17,5 mm (0.69") ø 75 mm (2.95") ø 98 mm (3.86") ø 180 mm (7.09") ø 220 mm (8.66") fig.70:radarsensorwithadapterflangedn100pn6 1 adapterfl...
Page 90
90 11 supplement vegapuls 69 • foundation fieldbus 47251-en-160815 vegapuls69,plastichornantennamitadapterflangeundrinsingconnection 3 2 1 170 mm (6.69") 62,5 mm (2.46") 20 mm (0.79") 34,7 mm (1.37") ø 75 mm (2.95") ø 98 mm (3.86") ø 180 mm (7.09") ø 220 mm (8.66") fig.71:vegapuls69,adapterflangedn1...
Page 91
91 11 supplement vegapuls 69 • foundation fieldbus 47251-en-160815 vegapuls 69, plastic horn antenna with mounting strap 125 mm (4.92") 2,5 mm (0.10") ø 75 mm (2.95") ø 107 mm (4.21") ø 115 mm (4.53") 300 mm (11.81") 19 mm (0.75") 98 mm (3.86") 6 mm (0.24") 8,5 mm (0.34") 9 mm (0.35") 85 mm (3.35") ...
Page 92
92 11 supplement vegapuls 69 • foundation fieldbus 47251-en-160815 vegapuls 69, metal-jacketed lens antenna 2 1 144 mm (5.67") 63 mm (2.48") 11,5 mm (0.45") ø 98 mm (3.86") g 1/8" x 8mm fig.73:vegapuls69,metal-jacketedlensantenna.Flangethicknessacc.Todrawing,flangedimensionsacc.To din/asme/jis. 1 ve...
Page 93
93 11 supplement vegapuls 69 • foundation fieldbus 47251-en-160815 vegapuls 69, metal-jacketed lens antenna with swivelling holder max. 10° 144 mm (5.67") 63 mm (2.48") 2 1 fig.75:vegapuls69,metal-jacketedlensantennaandswivellingholder 1 versionupto130°c(266°f) 2 versionupto200°c(392°f).
Page 94
94 11 supplement vegapuls 69 • foundation fieldbus 47251-en-160815 vegapuls 69, metal-jacketed lens antenna with swivelling holder and rinsing connection max. 10° 35 mm (1.38") 43 mm (1.69") 35 mm (1.38") 43 mm (1.69") 2 1 3 4 5 3 4 5 144 mm (5.67") 63 mm (2.48") fig.76:vegapuls69,metal-jacketedlens...
Page 95
95 11 supplement vegapuls 69 • foundation fieldbus 47251-en-160815 11.5 industrial property rights vega product lines are global protected by industrial property rights. Further information see www.Vega.Com. Vega produktfamilien sind weltweit geschützt durch gewerbliche schutzrechte. Nähere informat...
Page 96: Index
96 index vegapuls 69 • foundation fieldbus 47251-en-160815 index a adjustment 38, 43, 44 c change the language 45 copy sensor settings 49 curve indication – echo curve 46 d damping 44 date/time 48 default values 48 deviation 61 device id 52 displayed value 45 display lighting 46 e echo curve – memor...
Page 97
97 notes vegapuls 69 • foundation fieldbus 47251-en-160815.
Page 98
98 notes vegapuls 69 • foundation fieldbus 47251-en-160815.
Page 99
99 notes vegapuls 69 • foundation fieldbus 47251-en-160815.
Page 100
Printing date: vega grieshaber kg am hohenstein 113 77761 schiltach germany 47251-en-160815 all statements concerning scope of delivery, application, practical use and operat- ing conditions of the sensors and processing systems correspond to the information available at the time of printing. Subjec...