WEG MW500 User Manual - page 35
MW500 | 29
Powering up and Start-up
- English -
5.3.2.2 V VW Control Type (P0202 = 5)
Seq
Indication on the Display / Action
Seq
Indication on the Display / Action
1
6
Monitoring mode. Press the key
ENTER/MENU
to enter the 1st level of the programming mode.
Press the key to proceed with the Start-up
of the V V W.
2
7
The
PARAM group is selected, press the Keys
or until selecting the
STARTUP group.
If necessary, modify the content of “P0399
– Motor Rated Performance”, or press the
key for the next parameter.
3
8
When the
STARTUP group is selected press
the key
ENTER/MENU.
If necessary, modify the content of “P0400
– Motor Rated Voltage”, or press the key
for the next parameter.
4
9
Press
ENTER/MENU and with the keys and
set the value 5, which activates the control
mode V V W.
If necessary, modify the content of “P0401
– Motor Rated Current”, or press the key
for the next parameter.
5
10
Press
ENTER /MENU to save the modification
of P0202.
If necessary, modify the content of “P0402
– Motor Rated Rotation”, or press the key
for the next parameter.
Figure 5.5: Sequence of the Start-up group for V VW control