Quadra-Fire SANTAFEI-MBK Installation Manual - page 11
June 5, 2017
7019-230G
11
Santa Fe Pellet Insert
Keep sharp edge of
metal floor away from
power cord
Leveling Leg
Figure 11.1.Placetheinsertintothefacto-
ry-builtfirebox.Ensurethatthepowercord
can not be damaged by the sharp metal
edge.Youmayneedtocutoutanotchto
accommodatethecord.
Figure 11.2.Ensurethatthelevelinglegis
positionedoverthe2x4beforelevelingthe
insert.Minimum1”clearance.
NOTICE:
InCanadawhenusingafactory-builtchim-
neyitmustbesafetylisted,
Type UL103 HT (2100
o
F)
[1149
o
C] CLASS “A” orconformingtoCAN/ULC-
S629M, STANDARD FOR 650
o
C FACTORY-BUILT
CHIMNEYS.
F. Prefabricated Metal Chimney
Thechimneycanbeneworexisting,masonryorprefabricated
andmustmeetthefollowingminimumrequirements:
•Must be minimum 6 inch (152mm) inside diameter of
hightemperaturechimneylistedtoUL103HT(2100
o
F)
orULC-S628.
•Mustusecomponentsrequiredbythemanufacturerfor
installation.
•Mustmaintainclearancesrequiredbythemanufacturer
forinstallation.
•Refertomanufacturersinstructionsforinstallation
•This insert islistedtoASTME1509-12Standardand
isapprovedforinstallationintolistedfactory-builtzero
clearancefireplaceslistedtoUL127conformingtothe
followingspecificationsandinstructions:
•The original factory-built clearance fireplace chimney
cap must be re-installed after installing the approved
chimney liner meeting type UL 103 HT requirements
(2100°F)perUL1777.
•IfthechimneyisnotlistedasmeetingHTrequirements,
orifthefactorybuiltfireplacewastestedpriorto1998,a
fullheightlistedchimneylinermustbeinstalledfromthe
appliancefluecollartothechimneytop.
•Thelinermustbesecurelyattachedtotheinsertfluecollar
andthechimneytop.
•Theairflowofthefactory-builtzero-clearancefireplace
systemmustnotbealtered.Thefluelinertopsupport
attachmentmustnotreducetheairflowfortheexisting
air-cooledchimneysystem.
•Nodilutionairisallowedtoenterthechimney.
1.
Securethefireplacedamperintheopenposition.If
thiscannotbeaccomplished,itwillbenecessaryto
removethedamper
2.Seal damper area of chimney around chimney
connectorwithahightemperaturesealantorseal
insertagainstthefaceofthefireplace.
3.Bothmethodsmustberemovableandreplaceable
forcleaningandre-installation.
• Removingflooroffireplacemustnotweakenstructure
offireboxorreduceprotectionforcombustiblematerials.
• Finalapprovalofthisinstallationtypeiscontingentupon
theappropriatelocalauthorityhavingjurisdiction.
WARNING
E. Installation into a Masonry Fireplace
AllmodificationsthatcanbemadetoaFactoryBuiltFire-
placecanbemadetoaMasonryFireplace.
Inaddition
DO NOT
removeanybrickormortarfromthe
existingfireplace.
Risk of Fire!
Follow venting manufacturer’s clearances and
instructionswheninstallingventingsystem.
WARNING
1”
Example Removal of Factory-Built Fireplace Cont.