5 Set up with the display and adjustment module
VEGAPULS 69 • Profibus PA
47256-EN-170818
Setup: Settings, for example, to measurement loop name, medium,
application, vessel, adjustment, AI FB 1 Channel - scaling - damping
Display: Language setting, settings for the measured value indica-
tion as well as lighting
Diagnosis: Information, for example on the instrument status,
pointer, reliability, AI FB 1 simulation, echo curve
Further settings: Instrument units, false signal suppression, lineari-
zation, sensor address, PIN, date/time, reset, copy sensor data
Info: Instrument name, hardware and software version, date of
manufacture, instrument features
In the main menu item "Setup", the individual submenu items
should be selected one after the other and provided with the correct
parameters to ensure optimum adjustment of the measurement. The
procedure is described in the following.
Since the radar sensor is a distance measuring instrument, the
distance from the sensor to the product surface is measured. To
indicate the actual level, an allocation of the measured distance to the
percentage height must be carried out.
To perform the adjustment, enter the distance with full and empty ves-
sel, see the following example:
2
1
3
100%
0%
1 m
(39.37
")
35 m (1378
")
Fig. 11: Parameterisation example, Min./max. adjustment
1 Min. level = max. measuring distance
2 Max. level = min. measuring distance
3 Reference plane
If these values are not known, an adjustment with the distances of e.g.
10 % and 90 % is possible. Starting point for these distance specifica-
Setup - Adjustment