Wacker Neuson LTV6K Operator's manual - Operation
wc_tx004431gb_FM10.fm
68
Operation
LTV
5.12
Auto Mode (Remote Run)
The engine controller is capable of automatically starting the engine.
A scheduled run will begin only if the controller is in Auto Mode with no shut-down
alarm present. If the controller is in Stop/Reset Mode or Manual/Start Mode when a
scheduled run begins, the engine will not start. However, if the controller is set to
Auto Mode during a scheduled run, the engine will start.
A system designer can configure an external input to prevent a scheduled run.
If the engine is running “Off Load” in Auto Mode and a scheduled run configured to
“On Load” begins, the set is placed “On Load” for the duration of the schedule.
Front Panel
Configuration
This configuration mode allows the operator to fully configure the module through
its display without the use of the computer software.
Use the controller’s buttons to navigate through the menu and change the
parameters.
■ Next section (a)
■ Previous section (b)
■ Previous parameter (c)
■ Edit or save parameter (d)
■ Next parameter (e)
Editing a
Parameter
Note: Use the computer software for more comprehensive module configuration.
Note: If a PIN code is required, contact the generator supplier for the PIN code. If
the PIN code is lost or forgotten, return the controller to the Deep Sea factory to
remove the code. For security purposes, the PIN code automatically resets when
the editor is exited (manually or automatically).
1. To enter the editor mode, press the “Stop” (c) and “Auto” (d) buttons
simultaneously.
2. Press the up (a) and down (b) arrows to select the Configuration Editor or
Operator Editor. The selected editor flashes.
a
b
c
d
e
wc_gr014008