WEG CFW700 User Manual - page 19
14 | CFW700
Installation and Connection
E
ng
lis
h
R/L1 S/L2 T/L3
DC-
DC+ U/T1 V/T2 W/T3
BR
Ground
Ground
(f) Frame size E with degree of protection IP55
Figure 3.1: (a) to (f) Power terminals and grounding points - frame sizes A to E
3.2.2 Power / Grounding Wiring and Fuses
ATTENTION!
Use proper cable lugs for the power and grounding connection cables.
Refer to
,
and
for the
recommended wiring and fuses and
for the specifications of the power
terminals.
NOTE!
The gauges values presented in
and
are for reference only. Installation conditions and the
maximum permitted voltage drop shall be considered for the proper wiring sizing.
Input fuses
The fuses to be used at the input must be HS (High-Speed) type with I
2
t equal or lower the
value indicated in the
and
(consider extinction current value in cold situation (it is not the fusion value)), to
protect the inverter diode rectifiers and input wiring.
In order to meet UL requirements, use class J fuses at the inverter supply with a current not
higher than the values presented in
,
and
.