WEG CFW700 User Manual - page 46
CFW700 | 41
Keypad (HMI) and Basic Programming
E
ng
lis
h
Output
speed
Accelerating
ramp
Time
0 V (open)
0 V (open)
0 V (open)
24 V
24 V
24 V
DI5
DI4
DI6
P1011
P1013
P1014
P1015
P1016
P1017
P1018
P1012
Figure 4.6: Operation of the Multispeed Application
For the operation of the multispeed application, it is necessary to set the parameter P0221 or
P0222 to 7 = SoftPLC.
Definition:
The Function 1 of the Application in the parameters P0266 to P0268 represents the Multispeed
command.
The speed reference selection works according to the table below:
Table 4.3: Multispeed Reference
DI6
DI5
DI4
Speed Reference
0 V
0 V
0 V
P1011
0 V
0 V
24 V
P1012
0 V
24 V
0 V
P1013
0 V
24 V
24 V
P1014
24 V
0 V
0 V
P1015
24 V
0 V
24 V
P1016
24 V
24 V
0 V
P1017
24 V
24 V
24 V
P1018
If any digital input is selected for Multispeed, it should be considered as 0 V.
The parameters P1011 to P1018 define the speed reference value when the Multispeed is
operating.
The parameters related to this application are: