Installation and Connection
E
ng
lis
h
3.2.4 Grounding Connections
DANGER!
The inverter shall be connected to a Protective Ground (PE).
Use the minimum ground wiring gauge as indicated in the
and
Connect the inverter grounding connections to a ground bus bar, to a single
ground point, or to a common grounding point (impedance ≤ 10 Ω).
The neutral conductor of the network shall be solidly grounded; however,
this conductor shall not be used to ground the inverter.
It is necessary to use a copper cable with 10 mm
2
minimum or 2 cables with
the same wire gauge as specified in
,
and
for connecting the inverter to the
ground protection to be in accordance with IEC61800-5-1 since the leakage
current is greater than 3.5 mA AC.
3.2.5 Control Connections
The control connections (analog inputs/outputs and digital inputs/outputs), shall be performed
in connector XC1 of the CC700 Control Board. Functions and typical connections are presented
in