ABB i-bus KNX Product Manual - page 10
ABB i-bus
KNX
Device Technology
8 2CDC 508 101 D0201 | VAA/S x.230.2.1
KNX safety extra low voltage
SELV 30 V DC
Temperature range
Operation
Storage
Transport
-5 °C…+45 °C
-25 °C…+55 °C
-25 °C…+70 °C
Ambient conditions
Maximum air humidity
93 %, no condensation allowed
Design
Modular installation device (MDRC)
modular installation device, Pro M
Dimensions
VAA/S 6.230.1: 90 x 72 x 64.5 mm (H x W x D)
VAA/S 12.230.1: 90 x 144 x 64.5 mm(H x W x D)
Mounting width in space units
(modules at 18 mm)
4 or 8
Mounting depth
64.5 mm
Installation
On 35 mm mounting rail
to EN 60 715
Mounting position
As required
Weight (without batteries)
VAA/S 6.230.2.1:
VAA/S 12.230.2.1:
approx. 0.16 kg
approx. 0.28 kg
Housing/colour
Plastic housing, grey
Approvals
KNX to EN 50 090-1, -2
certification
CE mark
In accordance with the EMC guideline and low
voltage guideline
Device type
Application program
Maximum number of
communication objects
Maximum number of
group addresses
Maximum number of
associations
VAA/S 6.230.2.1
Valve Drive 6f 230V/…*
59
255
255
VAA/S 12.230.2.1
Valve Drive 12f 230V/…*
113
255
255
* … = current version number of the application program. Please observe the software information on our homepage for this purpose.
Note
The ETS and the current version of the device application program are required for programming.
The current version of the application program is available for download on the internet at
After import it is available in the ETS under ABB/Heating, Ventilation, Air
conditioning/Valve Drive Actuator
.
The device does not support the closing function of a KNX device in the ETS. If you inhibit access to all
devices of the project with a BCU code, it has no effect on this device. Reading out data and
programming is still possible.