ABB i-bus KNX Product Manual - page 36
ABB i-bus
KNX
Commissioning
34 2CDC 508 101 D0201 | VAA/S x.230.2.1
Control value on forced operation
in % [0…100]
Options: 0…30…100
This parameter determines the control value that the output should assume at forced operation.
If a control value is received via a 1 bit value, a value must be entered on parameter
, page 30. This value is used as the basis for calculation of the output control
at forced operation in %.
Enable communication object
"Status control value" 1 byte/1 bit
Options: no
1 bit
1 byte
The control status of the output is sent via this communication object.
1 bit:
The communication object
, page 45, (1 bit) and the following parameter
appears:
Send object value
Options:
no, update only
after a change
after request
after a change or request
no, update only:
The status is updated but not sent.
after a change:
The status is sent after a change.
after request:
The status is sent after a request.
after a change or request:
The status is sent after a change or a request.
Object value at control value > 0
Options: 1
0
If the communication object value is greater than 0, a telegram with the value 1 or 0 can be sent via
this parameter.
1 byte:
The communication object
, page 45,(1 byte) and the following
parameters are displayed: