ABB i-bus KNX Product Manual - page 40
ABB i-bus
KNX
Commissioning
38 2CDC 508 101 D0201 | VAA/S x.230.2.1
Example:
Value pair 1 (VP1)
Value pair 2 (VP2)
Control value in % [0…100]
10
Control value in % [0…100]
80
Valve position in % [0…100]
40
Valve position in % [0…100]
20
Implemented characteristic curve correction:
Control value
Valve position
0...10% 40%
20% 37%
30% 34%
40% 31%
50% 29%
60% 26%
70% 23%
80...100% 20%
Value pair 1
Control value in % [0...100]
Valve position in % [0...100]
Options: 0…100
Value pair 2
Control value in % [0...100]
Valve position in % [0...100]
Options: 0…100
The possibility of activating other value pairs allows different curve characteristics to be realised.
A total of four value pairs can be set.
100
VP1
VP2
40
10
80
Control value
in %
20
Valve position
in %