Commissioning
26 2CDC 508 101 D0201 | VAA/S x.230.2.1
3.2.2 Parameter
window
Manual operation
In this parameter window all the settings for manual operation can be made. For a detailed description of
manual operation see
, page 13.
Manual operation
Options: enabled
disabled
disable/enable via communication object
This parameter defines if the switch over between the operating states Manual operation and KNX
operation
is enabled or disabled via the button on the device or via a communication object.
enabled:
The operating states Manual operation and KNX operation can be toggled via button .
disabled:
Manual operation is generally disabled.
disable/enable via communication object:
The communication object Disable /enable man. operation
appears.
Telegram value:
0 = button enabled
1 = button disabled
If manual operation has been selected with the option enabled or the option disable/enable via
communication object
, two further parameters appear:
Reset manual operation to KNX operation
Options: no
after 1/3/10/30 minutes
This parameter determines how long manual operation remains activated or after how long switch
over to KNX operation occurs.
no:
Manual operation remains activated until it is deactivated again using the manual operation
button or using the communication object.
after X minutes:
Manual operation remains activated after the last operation of the button until
the parameterized time has timed out or it is deactivated again using the manual button .