Fairo(-hybrid) ECO-prestige
of
184
57
Configuration 2 - with horizontal section – gas type G20
(methane) and G25 (natural gas)
Minimum 1-metre vertical duct 130/200
Vertical elbow 130/200
Horizontal section maximum 5 metres 130/200
Wall duct 130/200 (A)
In configuration 2, the ceiling plate inside the fire must be removed.
Configuration 3 - horizontal section with horizontal elbow – gas type G20 (methane) and G25 (natural gas)
Minimum 1-metre vertical duct 130/200
Vertical elbow 130/200
Total horizontal section maximum 2.5 metres
Horizontal elbow 130/200
Wall duct 130/200 (A)
In configuration 3, the ceiling plate inside the fire must be removed.