KAL-FIRE ECO-prestige 105-59 Installation instructions manual - page 68
68
29.4
Home automation system
Step 1: Connect the cable (Figure 1) to the technical unit (Figures 2 and 3).
Figure 1
Figure 2
Figure 3
Step 2: The black wire connected to the 0/10V contact must be plugged into the phase of the output signal on the home automation
system. The black wire connected to the GND terminal must be connected to the ground terminal. Set the following values on the
home automation system:
> 1.5 V
Hybrid function
> 3.0 V
Request for heat, the fire will start
3.0 - 9.0 V
The height of the flames is regulated by modulation. Low or high position.
9.5 V
ECO mode
0 V
Fire is switched off
The remote control and the home automation system cannot be used at the same time. The remote control can be used if there is
no voltage on the two contacts.
In case of an error message, the system must always be reset using the remote control!