KEB COMBIVERT F6 Instructions For Use Manual - page 27
3.1.4 electrical operating conditions
3.1.4.1 Overvoltage
Overvoltage
Standard
Particularities
Overvoltage category
III
–
Table 5:
Overvoltage
3.1.4.2 Electromagnetic compatibility
Theindicatedvaluesareonlyvalidforunitswithexternalfilter.
eMc emitted interference
Standard
Particularities
Conducted emissions
C2
Thespecifiedvalueisonlyachievedinconnec-
tionwithanappropriate specialexternalfilter.
Also see
Radiated emissions
C2
Thespecifiedvalueisonlyachievedinconnec-
tionwithanappropriate specialexternalfilter.
Also see
Immunity
Standard
Particularities
Static discharges
8 kV
4 kV
AD (air discharge)
CD (contact discharge)
Burst - Ports for process
measurement control lines
and signal interfaces
2 kV
tested with 2 kV
Burst - Power ports
4 kV
tested with 4 kV
Surge - Power ports
1 kV
2 kV
Phase-phase
Phase-ground
Immunity to conducted distur-
bances, induced by radio-fre-
quencyfields
10 V
0.15...80 MHz
Electromagneticfields
10 V/m
3 V/m
1 V/m
80 MHz...1 GHz
1.4...2 GHz
2...2.7 GHz
Voltagefluctuations/
voltage dips
–
-15 %...+10 %
90 %
Frequency changes
–
≤2%
Voltage deviations
–
±10 %
Voltage unbalance
–
≤3%
Table 6:
Electromagnetic compatibility
27