4.2.5.4 Motor cable length for parallel operation of motors
The resulting motor cable length for parallel operation of motors, or parallel installation
with multiple cables arises from the following formula:
resultingmotorcablelength=∑singlelinelengthx√Number of motor lines
4.2.5.5 Motor cable cross-section
The cable cross-section of the motor cable depends on the real effective value of the
motor current, the line length, the type of the used cable (observe the manufacturer's
specifications)aswellastheambientconditionssuchasbundlingandtemperature.
Also observe the electrical regulations applicable for the operation site.
4.2.5.6 Interconnection of the motor
ATTENTION
Incorrect behavior of the motor!
► The connecting-up instructions of the motor manufacturer are al-
ways generally valid !
ATTENTION
Protect motor against voltage peaks !
► Drive converters switch at the output with high dv/dt. Voltage peaks
that endanger the insulation system at the motor can occur espe-
cially in case of long motor cables (>15 m). A motor choke, a dv/
dt-filterorsine-wavefiltercanbeusedtoprotectthemotorwith
regard to the operating mode.
56
cONNecTION OF THe POWer UNIT