3.3.5 control cabinet installation
Power loss for the control cabinet dimension
A lower value can be used here
depending on the operating mode/load.
Mounting distances
Dimen-
sion
Distance in mm
Distance in inch
C
A
B
D
D
A
150
6
B
100
4
C
30
1.2
D
0
0
X
1)
50
2
1)
Distance to preceding elements in the control cab-
inet door.
Figure 8:
Mounting distances
If construction-conditioned the control cabinet cannot be without indoor ventilation, ap-
propriatefiltersmustavoidsuctionofforeignobjects.
Direction of the air
flow
Front and side view of the coolant inlet
Coolant outlet
Coolant inlet
Figure 9:
Control cabinet ventilation
42
DIMeNSIONS AND WeIGHTS