Vacon 10 Quick Manual - page 11
monitoring & parameters
vacon
•
10
24-hour support +1 877 822 6606 • Email: usa@vacon.com
5
5.2 Quick setup parameters
(
Virtual menu, shows when par. 13.1 = 1
)
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.1
Motor nominal voltage
180
690
V
230
400
575
110
Check rating plate on the
motor
P1.2
Motor nominal fre-
quency
30
320
Hz
50,00
111
Check rating plate on the
motor
P1.3
Motor nominal speed
300
20000
rpm
1440
112
Default applies for a 4-pole
motor.
P1.4
Motor nominal current
0,2 x
I
Nunit
2,0 x
I
Nunit
A
I
Nunit
113
Check rating plate on the
motor
P1.5
Motor cos
0,30
1,00
0,85
120
Check rating plate on the
motor
P1.7
Current limit
0,2 x
I
Nunit
2 x
I
Nunit
A
1,5 x
I
Nunit
107
P1.15
Torque boost
0
1
0
109
0 = Not used
1 = Used
P2.1
Remote control place
1
2
1
172
1 = I/O terminal
2 = Fieldbus
(one selection removed)
P2.2
Start function
0
1
0
505
0 = Ramp 1 = Flying start
P2.3
Stop function
0
1
0
506
0 = Coasting 1 = Ramp
P3.1
Min frequency
0,00
P3.2
Hz
0,00
101
P3.2
Max frequency
P3.1
320
Hz
50,00
102
P3.3
I/O reference
0
4
3
117
0 = Preset Speeds (0-7)
1 = Keypad Reference
2 = Fieldbus Reference
3 = AI1 (API FULL &
LIMITED)
4 = AI2
(API FULL)
P3.4
Preset speed 0
0,00
P3.2
Hz
5,00
124
Activated by digital inputs
P3.5
Preset speed 1
0,00
P3.2
Hz
10,00
105
Activated by digital inputs
P3.6
Preset speed 2
0,00
P3.2
Hz
15,00
106
Activated by digital inputs
P3.7
Preset speed 3
0,00
P3.2
Hz
20,00
126
Activated by digital inputs
P4.2
Acceleration time
0,1
3000
s
1,0
103
Acceleration time from 0
Hz to maximum frequency
Table 4: Quick setup parameters