- With above-mentioned fuses, the drive can be connected to power supply the short
circuit current of which is max. 50kA
- Use cables with heat resistance of at least +70°C.
- The fuses function also as cable overload protection.
- These instructions apply only to cases with one motor and one cable connection
from the frequency converter to the motor.
- To fulfil standard EN61800-5-1, the protective conductor should be at least 10mm2
Cu or 16mm Al. Another possibility is to use an additional protective conductor of
at least the same size as the original one.
Vacon 10 power ratings
Cable and fuse require-
ments
(See detailed data in Vacon
10 User Manual at:
www.vacon.com)
380 - 480V
208-240V 3~
575V
Frame
Fuse
(A)
Mains cable
Cu (mm
2
)
Terminal cable min-max (mm
2
)
Main & earth
Control & relay
MI1
6
3*1.5+1.5
1.5-4
0.5-1.5
MI2
10
MI3
20
3*2.5+2.5
1.5-6
115V
208 - 240V 1~
MI1
10
2*1.5+1.5
1.5-4
MI2
20
2*2.5+2.5
MI3
32
2*6+6
1.5-6
Mains voltage 115 V, 50/60 Hz, 1~ series
Frecuency
converter
type
Rated loadability
Motor
shaft
power
Nominal
input current
Mechani-
cal size
100% contin.
current I
N
[ A ]
150% overload
current [ A ]
P
[ HP ]
[ A ]
0001
1,7
2,6
0.33
9,2
MI2
0002
2,4
3,6
0.5
11,6
MI2
0003
2,8
4,2
0.75
12,4
MI2
0004
3,7
5,6
1
15
MI2
0005
4,8
7,2
1.5
16,5
MI3