Vacon 10 Quick Manual - page 18
17
•
vacon
monitoring & parameters
Tel. +1 877 822 6606 • Fax +1 717 264 3115
5
5.9 Digital and analogue outputs (Control panel: Menu PAR -> P7)
NOTE! These parameters are shown, when P13.1 = 0.
Code
Parameter
Min
Max
Unit
Default
ID
Selections
Only in API FULL
P7.1
Relay output 1
content
0
11
P7.6
2
313
0 = Not used
1 = Ready
2 = Run
3 = Fault
4 = Fault Inverted
5 = Alarm
6 = Reversed
7 = At Speed
8 = Motor Regulator Active
9 = FBControlWord.Bit13
10 = FBControlWord.Bit14
11 = FBControlWord.Bit15
In all API versions
P7.2
Relay output 2
content
0
11
3
314 As parameter 7.1
Only in API FULL
P7.3
Digital output 1
content
0
11
1
312 As parameter 7.1
P7.4
Analogue output
function
0
4
1
307
0 = Not in use
1 = Output freq. (0-f
max
)
2 = Output current (0-I
nMotor
)
3 = Torque (0-Nominal
torque)
4 = PI controller output
P7.5
Analogue output
minimum
0
1
1
310
0 = 0 mA
1= 4 mA
Only in API Limited
P7.6
Relay 2 invert
0
1
0
489 1= Relay 2 inverted
Table 11: Digital and analogue inputs