Vacon 10 Quick Manual - page 28
27
•
vacon
general data
Tel. +1 877 822 6606 • Fax +1 717 264 3115
7
Note: The input currents are calculated values with 100 kVA line transformer supply.
Quick Modbus setup
Mains voltage 575 V, 50/60 Hz, 3~ series
Frecuency
converter
type
Rated loadability
Motor
shaft
power
Nominal
input current
Mechani-
cal size
100% contin.
current I
N
[ A ]
150% overload
current [ A ]
P
[ HP ]
[ A ]
0002
1,7
2,6
1
2
MI3
0003
2,7
4,2
2
3,6
MI3
0004
3,9
5,9
3
5
MI3
0006
6,1
9,2
5
7,6
MI3
0009
9
13,5
10
10,4
MI3
0011
11
16,5
10
14,1
MI3
1
A: Select Fieldbus as remote control place: P2.1 to 3 – Fieldbus
B: Set Modbus RTU protocol to “ON”: S2.2 to 1 – Modbus
2
A. Set Control Word to “0” (2001)
B. Set Control Word to “1” (2001)
C. Frequency converter status is RUN
D. Set Reference value to “5000” (50,00%) (2003)
E. Actual Speed is 5000 (25.00 Hz if MinFreq is 0.00 Hz and MaxFreq is 50.00 Hz)
F. Set Control Word to “0” (2001)
G. Frequency converter status is STOP