5.8 Analogue inputs (Control panel: Menu PAR -> P6)
NOTE! These parameters are shown, when P13.1 = 0.
Code
Parameter
Min
Max
Unit
Default
ID
Note
Only in API FULL & LIMITED
P6.1
AI1 Signal range
0
3
0
379
API FULL and LIMITED:
0 = Voltage 0…10 V
1 = Voltage 2…10 V
API LIMITED ONLY:
2 = Current 0…20 mA
3 = Current 4…20 mA
NOTE: When using API
LIMITED, select the volt-
age/current range also
with the dip switch
P6.2
AI1 filter time
0,0
10,0
s
0,1
378 0 = no filtering
P6.3
AI1 Custom min
-100,0
100,0
%
0,0
380 0,0 = no min scaling
P6.4
AI1 Custom max
-100,0
100,0
%
100,0
381 100,0 = no max scaling
Only in API FULL
P6.5
AI2 signal range
2
3
3
390
2 = Current 0…20 mA
3 = Current 4…20 mA
P6.6
AI2 filter time
0,0
10,0
s
0,1
389 0 = no filtering
P6.7
AI2 Custom min
-100,0
100,0
%
0,0
391 0,0 = no min scaling
P6.8
AI2 Custom max
-100,0
100,0
%
100,0
392 100,0 = no max scaling
Table 10: Analogue inputs